7.10
Under impedance protection for generators and
transformers ZGVPDIS
7.10.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/
IEEEidentification
Under impedance function for
generators and transformers
ZGVPDIS
S00346 V1 EN
21G
7.10.2
Functionality
The under impedance protection is a three zone full scheme impedance protection
using offset mho characteristics for detecting faults in the generator, generator-
transformer and transmission system. The three zones have fully independent
measuring loops and settings. The functionality also comprises an under voltage seal-
in feature to ensure issuing of a trip even if the current transformer goes into saturation
and, in addition, the positive-sequence-based load encroachment feature for the
second and the third impedance zone. Built-in compensation for the step-up
transformer vector group connection is available.
7.10.3
Function block
ZGVPDIS
I3P*
U3P*
BLOCK
BLKZ
BLKUV
TRIP
TRZ1
TRZ2
TRZ3
TRUV
START
STZ1
STZ2
STZ3
STUV
IEC14000018-1-en.vsd
IEC14000018 V1 EN
Figure 145:
ZGVPDIS function block
1MRK502052-UEN B
Section 7
Impedance protection
319
Technical manual
Содержание Relion REG670
Страница 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Страница 2: ......
Страница 44: ...38 ...
Страница 58: ...52 ...
Страница 80: ...74 ...
Страница 106: ...100 ...
Страница 482: ...476 ...
Страница 548: ...542 ...
Страница 570: ...564 ...
Страница 600: ...594 ...
Страница 608: ...602 ...
Страница 630: ...624 ...
Страница 862: ...856 ...
Страница 1094: ...1088 ...
Страница 1226: ...1220 ...
Страница 1250: ...1244 ...
Страница 1297: ...1291 ...