Name
Values (Range)
Unit
Step
Default
Description
UnderTrigOp02
Off
On
-
-
Off
Use under level trigger for analog channel
2 (on) or not (off)
UnderTrigLe02
0 - 200
%
1
50
Under trigger level for analog channel 2 in
% of signal
OverTrigOp02
Off
On
-
-
Off
Use over level trigger for analog channel 2
(on) or not (off)
OverTrigLe02
0 - 5000
%
1
200
Over trigger level for analog channel 2 in
% of signal
NomValue03
0.0 - 999999.9
-
0.1
0.0
Nominal value for analog channel 3
UnderTrigOp03
Off
On
-
-
Off
Use under level trigger for analog channel
3 (on) or not (off)
UnderTrigLe03
0 - 200
%
1
50
Under trigger level for analog channel 3 in
% of signal
OverTrigOp03
Off
On
-
-
Off
Use over level trigger for analog channel 3
(on) or not (off)
OverTrigLe03
0 - 5000
%
1
200
Overtrigger level for analog channel 3 in %
of signal
NomValue04
0.0 - 999999.9
-
0.1
0.0
Nominal value for analog channel 4
UnderTrigOp04
Off
On
-
-
Off
Use under level trigger for analog channel
4 (on) or not (off)
UnderTrigLe04
0 - 200
%
1
50
Under trigger level for analog channel 4 in
% of signal
OverTrigOp04
Off
On
-
-
Off
Use over level trigger for analog channel 4
(on) or not (off)
OverTrigLe04
0 - 5000
%
1
200
Over trigger level for analog channel 4 in
% of signal
NomValue05
0.0 - 999999.9
-
0.1
0.0
Nominal value for analog channel 5
UnderTrigOp05
Off
On
-
-
Off
Use under level trigger for analog channel
5 (on) or not (off)
UnderTrigLe05
0 - 200
%
1
50
Under trigger level for analog channel 5 in
% of signal
OverTrigOp05
Off
On
-
-
Off
Use over level trigger for analog channel 5
(on) or not (off)
OverTrigLe05
0 - 5000
%
1
200
Over trigger level for analog channel 5 in
% of signal
NomValue06
0.0 - 999999.9
-
0.1
0.0
Nominal value for analog channel 6
UnderTrigOp06
Off
On
-
-
Off
Use under level trigger for analog channel
6 (on) or not (off)
UnderTrigLe06
0 - 200
%
1
50
Under trigger level for analog channel 6 in
% of signal
OverTrigOp06
Off
On
-
-
Off
Use over level trigger for analog channel 6
(on) or not (off)
OverTrigLe06
0 - 5000
%
1
200
Over trigger level for analog channel 6 in
% of signal
NomValue07
0.0 - 999999.9
-
0.1
0.0
Nominal value for analog channel 7
UnderTrigOp07
Off
On
-
-
Off
Use under level trigger for analog channel
7 (on) or not (off)
Table continues on next page
Section 16
1MRK502052-UEN B
Monitoring
924
Technical manual
Содержание Relion REG670
Страница 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Страница 2: ......
Страница 44: ...38 ...
Страница 58: ...52 ...
Страница 80: ...74 ...
Страница 106: ...100 ...
Страница 482: ...476 ...
Страница 548: ...542 ...
Страница 570: ...564 ...
Страница 600: ...594 ...
Страница 608: ...602 ...
Страница 630: ...624 ...
Страница 862: ...856 ...
Страница 1094: ...1088 ...
Страница 1226: ...1220 ...
Страница 1250: ...1244 ...
Страница 1297: ...1291 ...