14.2.11.2
Functionality
The interlocking for transformer bay (AB_TRAFO) function is used for a transformer
bay connected to a double busbar arrangement according to figure
. The function
is used when there is no disconnector between circuit breaker and transformer.
Otherwise, the interlocking for line bay (ABC_LINE) function can be used. This
function can also be used in single busbar arrangements.
QB1
QB2
QC1
QA1
QC2
WA1 (A)
WA2 (B)
QA2
QC3
T
QC4
QB4
QB3
QA2 and QC4 are not
used in this interlocking
AB_TRAFO
en04000515.vsd
IEC04000515 V1 EN
Figure 327:
Switchyard layout AB_TRAFO
Section 14
1MRK502052-UEN B
Control
698
Technical manual