13.3.8
Technical data
Table 361:
VDSPVC technical data
Function
Range or value
Accuracy
Operate value, block of main fuse
failure
(10.0-80.0)% of UBase
±0.5% of Ur
Reset ratio
<110%
Operate time, block of main fuse
failure at 1 to 0 x U
r
Min. = 5 ms
–
Max. = 15 ms
Reset time, block of main fuse
failure at 0 to 1 x U
r
Min. = 15 ms
–
Max. = 30 ms
Operate value, alarm for pilot
fuse failure
(10.0-80.0)% of UBase
±0.5% of Ur
Reset ratio
<110%
–
Operate time, alarm for pilot fuse
failure at 1 to 0 x U
r
Min. = 5 ms
–
Max. = 15 ms
Reset time, alarm for pilot fuse
failure at 0 to 1 x U
r
Min. = 15 ms
–
Max. = 30 ms
1MRK502052-UEN B
Section 13
Secondary system supervision
623
Technical manual