When the position of the SXSWI is substituted, its IEC 61850-8-1 data
object is marked as “substituted", in addition to the substituted
quality, but the position quality of the connected SCSWI is not
dependent on the substitution indication in the quality, so it does not
show that it is derived from a substituted value.
Time diagrams
There are two timers for supervising of the execute phase,
tStartMove
and
tIntermediate
.
tStartMove
supervises that the primary device starts moving after the
execute output pulse is sent.
tIntermediate
defines the maximum allowed time for
intermediate position. Figure
explains these two timers during the execute phase.
EXE_CL
tStartMove timer
OPENPOS
CLOSEPOS
tIntermediate timer
t1
t2
tStartMove
tIntermediate
if t1 > tStartMove then
"switch-not-start-moving"
attribute in 'cause' is set
if t2 > tIntermediate then
"persisting-intermediate-state"
attribute in 'cause' is set
Close pulse duration
AdaptivePulse = TRUE
en05000097.vsd
IEC05000097 V1 EN
Figure 347:
The timers tStartMove and tIntermediate
The timers
tOpenPulse
and
tClosePulse
are the length of the execute output pulses to
be sent to the primary equipment. Note that the output pulses for open and close
command can have different pulse lengths. The pulses can also be set to be adaptive
with the configuration parameter
AdaptivePulse
. Figure
the execute output pulse. The
AdaptivePulse
parameter will have effect on both
execute output pulses.
1MRK502052-UEN B
Section 14
Control
733
Technical manual
Содержание Relion REG670
Страница 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Страница 2: ......
Страница 44: ...38 ...
Страница 58: ...52 ...
Страница 80: ...74 ...
Страница 106: ...100 ...
Страница 482: ...476 ...
Страница 548: ...542 ...
Страница 570: ...564 ...
Страница 600: ...594 ...
Страница 608: ...602 ...
Страница 630: ...624 ...
Страница 862: ...856 ...
Страница 1094: ...1088 ...
Страница 1226: ...1220 ...
Страница 1250: ...1244 ...
Страница 1297: ...1291 ...