Figure 144:
STTIPHIZ alarm and trip logic
If the fault resistance R
f
is smaller than R
Alarm
and last longer than set alarm delay,
output ALARM is set. If the fault resistance R
f
is smaller than R
Trip
, output signal
TRIP is set after the calculated time. For trip time delay, see fig
7.9.10
Technical data
Table 143:
STTIPHIZ technical data
Function
Range or value
Accuracy
Fault resistance sensitivity
Can be reached at
steady state operating
condition of the
machine
50 kΩ
Typically
10 kΩ
Injection frequency
(50.000 - 250.000) Hz
±0.1 Hz
Injection voltage
240 V
Trip limit of fault resistance
(100 - 10000)Ω
±5% of 1 kΩ at R
f
≤ 1 kΩ
±10% of set value at R
f
> 1 kΩ
Alarm limit of fault resistance
(100 - 100000)Ω
±5% of 1 kΩ at R
f
≤ 1 kΩ
±10% of 10 kΩ at 1 kΩ < R
f
≤ 10 kΩ
±50% of set value at R
f
> 10 kΩ
Operate time, start at R
f
~ 0Ω
and filter length = 1 s
1.00 s typically
-
Operate time, trip at R
f
~ 0Ω and
filter length = 1 s
3.00 s typically
-
Alarm time delay at R
f
~ 0Ω and
filter length = 1 s
(0.00 - 600.00) s
±0.2% or ± 2.00 s whichever is greater
Section 7
1MRK502052-UEN B
Impedance protection
318
Technical manual
Содержание Relion REG670
Страница 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Страница 2: ......
Страница 44: ...38 ...
Страница 58: ...52 ...
Страница 80: ...74 ...
Страница 106: ...100 ...
Страница 482: ...476 ...
Страница 548: ...542 ...
Страница 570: ...564 ...
Страница 600: ...594 ...
Страница 608: ...602 ...
Страница 630: ...624 ...
Страница 862: ...856 ...
Страница 1094: ...1088 ...
Страница 1226: ...1220 ...
Страница 1250: ...1244 ...
Страница 1297: ...1291 ...