STRNULL is a string, fixed to an empty string (null) value
•
ZEROSMPL is a channel index, fixed to 0 value
•
GRP_OFF is a group signal, fixed to 0 value
15.10
Boolean 16 to Integer conversion B16I
15.10.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Boolean 16 to integer conversion
B16I
-
-
Boolean 16 to integer conversion function B16I is used to transform a set of 16 binary
(logical) signals into an integer.
15.10.2
Function block
IEC07000128-2-en.vsd
B16I
BLOCK
IN1
IN2
IN3
IN4
IN5
IN6
IN7
IN8
IN9
IN10
IN11
IN12
IN13
IN14
IN15
IN16
OUT
IEC07000128 V2 EN
Figure 399:
B16I function block
15.10.3
Signals
Table 588:
B16I Input signals
Name
Type
Default
Description
BLOCK
BOOLEAN
0
Block of function
IN1
BOOLEAN
0
Input 1
IN2
BOOLEAN
0
Input 2
IN3
BOOLEAN
0
Input 3
IN4
BOOLEAN
0
Input 4
Table continues on next page
1MRK502052-UEN B
Section 15
Logic
837
Technical manual
Содержание Relion REG670
Страница 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Страница 2: ......
Страница 44: ...38 ...
Страница 58: ...52 ...
Страница 80: ...74 ...
Страница 106: ...100 ...
Страница 482: ...476 ...
Страница 548: ...542 ...
Страница 570: ...564 ...
Страница 600: ...594 ...
Страница 608: ...602 ...
Страница 630: ...624 ...
Страница 862: ...856 ...
Страница 1094: ...1088 ...
Страница 1226: ...1220 ...
Страница 1250: ...1244 ...
Страница 1297: ...1291 ...