REFPDIF is not sensitive to inrush and overexcitation currents. The only danger is an
eventual current transformer saturation.
REFPDIF has only one operate-bias characteristic, which is described in the table
and shown in Figure
.
Table 67:
Data of the operate-bias characteristic of REFPDIF
Default sensitivity Idmin
(zone 1)
Max. base
sensitivity Idmin
(zone 1)
Min. base sensitivity
Idmin (zone 1)
End of zone
1
First slope Second
slope
% IBase
% IBase
% IBase
% IBase
%
%
30
5
100
125
70
100
The differential protection REFPDIF calculates a differential current and a bias
current. In case of internal earth faults, the differential current is theoretically equal to
the total earth-fault current. The bias current is supposed to give stability to REFPDIF.
The bias current is a measure of how high the currents are and how difficult the
conditions are under which the CTs operate. With a high bias, difficult conditions can
be suspected, and it will be more likely that the calculated differential current has a
component of a false current, primarily due to CT saturation. This “law” is formulated
by the operate-bias characteristic. This characteristic divides the Idiff - Ibias plane in
two areas. The area above the operate-bias characteristic is the operate area, while the
one below is the block area, see Figure
bias current
in per unit
Zero-
sequence
diff. current
in per unit
0
1
2
3
4
5
IdMin
Section 1
Operate
conditionally
I
operate
slope = ----------------* 100 %
I
restrain
Sec. 2
Section 3
The characteristic
can be moved
up and down
(vertically)
by changing
the setting IdMin
End Section 1
End Section 2
IdMin range: 0.04
–
1.00 IBase
Reset Ratio in all sections:
0.95 (a constant)
Slope 70%
Restrain
Slope 100%
Characteristic if
IdMin = 1.0 pu
IEC98000017-5-en.vsd
D
D
0
1
2
3
4
5
6
IEC98000017-5 V1 EN
Figure 63:
Operate - bias characteristic of the Restricted earth-fault protection,
low impedance REFPDIF
1MRK502052-UEN B
Section 6
Differential protection
171
Technical manual
Содержание Relion REG670
Страница 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Страница 2: ......
Страница 44: ...38 ...
Страница 58: ...52 ...
Страница 80: ...74 ...
Страница 106: ...100 ...
Страница 482: ...476 ...
Страница 548: ...542 ...
Страница 570: ...564 ...
Страница 600: ...594 ...
Страница 608: ...602 ...
Страница 630: ...624 ...
Страница 862: ...856 ...
Страница 1094: ...1088 ...
Страница 1226: ...1220 ...
Страница 1250: ...1244 ...
Страница 1297: ...1291 ...