21.4.3
Wall mounting
21.4.3.1
Overview
All case sizes, 1/2 x 19”, 3/4 x 19”,1/1 x 19”, can be wall mounted. It is also possible
to mount the IED on a panel or in a cubicle.
Use only the screws included in the mounting kit when mounting the
plates and the angles on the IED. Screws with wrong dimension may
damage the PCBs inside the IED.
If fiber cables are bent too much, the signal can be weakened. Wall
mounting is therefore not recommended for any communication
modules with fiber connection.
21.4.3.2
Mounting procedure for wall mounting
IEC130 00266-1-en.vsd
1
2
3
4
5
6
IEC13000266 V1 EN
Figure 558:
Wall mounting details.
Section 21
1MRK502052-UEN B
IED hardware
1210
Technical manual