The implementation for IEC 61850 quality data handling is restricted
to a simple level. If quality data validity is GOOD then the
DATAVALID output will be HIGH. If quality data validity is
INVALID, QUESTIONABLE, OVERFLOW, FAILURE or OLD
DATA then the DATAVALID output will be LOW.
18.11
GOOSE function block to receive a measurand value
GOOSEMVRCV
18.11.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
GOOSE function block to receive a
measurand value
GOOSEMVRCV
-
-
18.11.2
Functionality
GOOSEMVRCV is used to receive measured value using IEC 61850 protocol via
GOOSE.
18.11.3
Function block
IEC10000251-1-en.vsd
GOOSEMVRCV
BLOCK
^MVOUT
DATAVALID
COMMVALID
TEST
IEC10000251 V1 EN
Figure 488:
GOOSEMVRCV function block
18.11.4
Signals
Table 800:
GOOSEMVRCV Input signals
Name
Type
Default
Description
BLOCK
BOOLEAN
0
Block of function
Section 18
1MRK502052-UEN B
Station communication
1070
Technical manual