IEC05000652 V2 EN
Figure 196:
Calibration curves
The first current and voltage phase in the group signals will be used as reference and
the amplitude and angle compensation will be used for related input signals.
Analog outputs (Monitored data) from the function can be used for service values or
in the disturbance report. The active power is provided as MW value: P, or in percent
of base power: PPERCENT. The reactive power is provided as Mvar value: Q, or in
percent of base power: QPERCENT.
8.10.8
Technical data
Table 220:
GUPPDUP technical data
Function
Range or value
Accuracy
Power level
for Step 1 and Step 2
(0.0–500.0)% of
SBase
± 1.0% of S
r
at S ≤ S
r
± 1.0% of S at S > S
r
where
1.732
r
r
r
S
U I
=
×
×
Characteristic angle
for Step 1 and Step 2
(-180.0–180.0) degrees
± 2.0 degrees
Independent time delay to
operate for Step 1 and Step 2 at
2 to 0.5 x S
r
and
k=0.000
(0.01-6000.00) s
± 0.2% or ± 40 ms whichever is
greater
Section 8
1MRK502052-UEN B
Current protection
426
Technical manual