18.6.4
Function status auto-recloser for IEC 60870-5-103 I103AR
18.6.4.1
Functionality
I103AR is a function block with defined functions for autorecloser indications in
monitor direction. This block includes the
FunctionType
parameter, and the
information number parameter is defined for each output signal.
18.6.4.2
Identification
Function description
Function block
name
IEC 60617
identification
ANSI/IEEE C37.2
device number
Function status auto-recloser for IEC
60870-5-103
I103AR
-
-
18.6.4.3
Function block
I103AR
BLOCK
16_ARACT
128_CBON
130_BLKD
IEC10000289-2-en.vsd
IEC10000289 V2 EN
Figure 473:
I103AR function block
18.6.4.4
Signals
Table 751:
I103AR Input signals
Name
Type
Default
Description
BLOCK
BOOLEAN
0
Block of status reporting
16_ARACT
BOOLEAN
0
Information number 16, auto-recloser active
128_CBON
BOOLEAN
0
Information number 128, circuit breaker on by auto-
recloser
130_BLKD
BOOLEAN
0
Information number 130, auto-recloser blocked
18.6.4.5
Settings
Table 752:
I103AR Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
FunctionType
1 - 255
-
1
1
Function type (1-255)
Section 18
1MRK502052-UEN B
Station communication
1034
Technical manual
Содержание Relion REG670
Страница 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Страница 2: ......
Страница 44: ...38 ...
Страница 58: ...52 ...
Страница 80: ...74 ...
Страница 106: ...100 ...
Страница 482: ...476 ...
Страница 548: ...542 ...
Страница 570: ...564 ...
Страница 600: ...594 ...
Страница 608: ...602 ...
Страница 630: ...624 ...
Страница 862: ...856 ...
Страница 1094: ...1088 ...
Страница 1226: ...1220 ...
Страница 1250: ...1244 ...
Страница 1297: ...1291 ...