Table 166:
EFPIOC Output signals
Name
Type
Description
TRIP
BOOLEAN
Trip signal
8.3.5
Settings
Table 167:
EFPIOC Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Off
On
-
-
Off
Operation Off / On
IN>>
5 - 2500
%IB
1
200
Operate residual current level in % of
IBase
Table 168:
EFPIOC Group settings (advanced)
Name
Values (Range)
Unit
Step
Default
Description
StValMult
0.5 - 5.0
-
0.1
1.0
Multiplier for operate current level
Table 169:
EFPIOC Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
GlobalBaseSel
1 - 12
-
1
1
Selection of one of the Global Base Value
groups
8.3.6
Monitored data
Table 170:
EFPIOC Monitored data
Name
Type
Values (Range)
Unit
Description
IN
REAL
-
A
Residual current
8.3.7
Operation principle
The sampled analog residual currents are pre-processed in a discrete Fourier filter
(DFT) block. From the fundamental frequency components of the residual current, as
well as from the sample values the equivalent RMS value is derived. This current
value is fed to the Instantaneous residual overcurrent protection (EFPIOC). In a
comparator the RMS value is compared to the set operation current value of the
function (
IN>>
). If the residual current is larger than the set operation current a signal
from the comparator is set to true. This signal will, without delay, activate the output
signal TRIP.
Section 8
1MRK502052-UEN B
Current protection
352
Technical manual
Содержание Relion REG670
Страница 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Страница 2: ......
Страница 44: ...38 ...
Страница 58: ...52 ...
Страница 80: ...74 ...
Страница 106: ...100 ...
Страница 482: ...476 ...
Страница 548: ...542 ...
Страница 570: ...564 ...
Страница 600: ...594 ...
Страница 608: ...602 ...
Страница 630: ...624 ...
Страница 862: ...856 ...
Страница 1094: ...1088 ...
Страница 1226: ...1220 ...
Страница 1250: ...1244 ...
Страница 1297: ...1291 ...