![ABB Relion REG670 Скачать руководство пользователя страница 547](http://html.mh-extra.com/html/abb/relion-reg670/relion-reg670_technical-manual_4698547.webp)
will be reduced compared to the normal operating condition. Therefore, there is a
possibility to reduce the sensitivity of the protection when the generator circuit
breaker is open.
With the setting
CBexists
change of the sensitivity is enabled. If the binary input signal
CBCLOSED is activated the set sensitivity is valid. If the generator circuit breaker is
opened the binary input CBCLOSED is deactivated and the sensitivity is changed.
This is done by changing the factor
Beta
which is multiplied with a set constant
FactorCBopen
.
In addition to the binary outputs also some analog outputs are available from the
protection function in order to enable easier commissioning:
E3: the magnitude of the 3
rd
harmonic voltage induced in the stator given in primary
volts
UN3: the magnitude of the 3
rd
harmonic voltage measured in the neutral point of the
generator
UT3: the magnitude of the 3
rd
harmonic voltage measured in the terminal point of the
generator
ANGLE: the angle between the phasors UN3 and UT3 given in radians
DU3: the magnitude of the 3
rd
harmonic differential voltage
BU3: the magnitude of the 3
rd
harmonic bias voltage
UN: the fundamental frequency voltage measured in the neutral point of the generator
9.6.8
Technical data
Table 303:
STEFPHIZ technical data
Function
Range or value
Accuracy
Fundamental frequency level UN
(95% Stator EF)
(1.0–50.0)% of
UBase
±0.25% of U
r
Third harmonic differential level
(0.5–10.0)% of
UBase
±0.25% of U
r
Third harmonic differential block
level
(0.1–10.0)% of
UBase
±0.25% of U
r
Independent time delay to
operate for fundamental UN >
protection at 0 to 1.2 x UNFund>
(0.020–60.000) s
±0.2% or ±40 ms whichever is
greater
Independent time delay to
operate for 3rd harm-based
protection at 0 to 5 x UN3rdH<
(0.020–60.000) s
±0.2% or ±40 ms whichever is
greater
Filter characteristic:
Fundamental
Third harmonic
Reject third harmonic by 1–40
Reject fundamental harmonic by
1–40
-
1MRK502052-UEN B
Section 9
Voltage protection
541
Technical manual
Содержание Relion REG670
Страница 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Страница 2: ......
Страница 44: ...38 ...
Страница 58: ...52 ...
Страница 80: ...74 ...
Страница 106: ...100 ...
Страница 482: ...476 ...
Страница 548: ...542 ...
Страница 570: ...564 ...
Страница 600: ...594 ...
Страница 608: ...602 ...
Страница 630: ...624 ...
Страница 862: ...856 ...
Страница 1094: ...1088 ...
Страница 1226: ...1220 ...
Страница 1250: ...1244 ...
Страница 1297: ...1291 ...