8.15.3
Function block
IEC12000027-1-en.vsd
GSPTTR
I3P*
BLOCK
SETLKOUT
RESET
IBASE
TRIP
START
LOCKOUT
BLKRECL
IEC12000027 V1 EN
Figure 212:
GSPTTR function block
8.15.4
Signals
Table 248:
GSPTTR Input signals
Name
Type
Default
Description
I3P
GROUP
SIGNAL
-
Current Group Connection
BLOCK
BOOLEAN
0
Block of function
SETLKOUT
BOOLEAN
0
Input for forcing the output LOCKOUT
RSTLKOUT
BOOLEAN
0
Reset of the output LOCKOUT and theta to 0%
Table 249:
GSPTTR Output signals
Name
Type
Description
TRIP
BOOLEAN
General trip signal from the function
START
BOOLEAN
General start signal from the function
LOCKOUT
BOOLEAN
Trip lockout output (latched)
BLKRECL
BOOLEAN
Block machine closing command
8.15.5
Settings
Table 250:
GSPTTR Group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Off
On
-
-
Off
Operation Off / On
I>
105.0 - 900.0
%
0.1
110.0
Current pickup value for overload
protection
ReclsLevTheta
1.0 - 100.0
%
0.1
70.0
Level for theta in percent below which the
generator can be reconnected to grid
k1
1.00 - 200.00
s
0.01
37.50
Time multiplier for thermal charact.
operate time delay
AutoLockout
Off
On
-
-
Off
Auto lockout enables activation of
LOCKOUT when TRIP is set
tPulse
0.5 - 10.0
s
0.1
1.0
Minimum pulse length of the trip signal
Table continues on next page
Section 8
1MRK502052-UEN B
Current protection
454
Technical manual
Содержание Relion REG670
Страница 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Страница 2: ......
Страница 44: ...38 ...
Страница 58: ...52 ...
Страница 80: ...74 ...
Страница 106: ...100 ...
Страница 482: ...476 ...
Страница 548: ...542 ...
Страница 570: ...564 ...
Страница 600: ...594 ...
Страница 608: ...602 ...
Страница 630: ...624 ...
Страница 862: ...856 ...
Страница 1094: ...1088 ...
Страница 1226: ...1220 ...
Страница 1250: ...1244 ...
Страница 1297: ...1291 ...