![ABB Relion REG670 Скачать руководство пользователя страница 904](http://html.mh-extra.com/html/abb/relion-reg670/relion-reg670_technical-manual_4698904.webp)
Table 658:
SSCBR Output signals
Name
Type
Description
OPENPOS
BOOLEAN
CB is in open position
CLOSEPOS
BOOLEAN
CB is in closed position
INVDPOS
BOOLEAN
CB is in Invalid Position
TRCMD
BOOLEAN
Open command issued to CB
TRVTOPAL
BOOLEAN
CB open travel time exceeded set value
TRVTCLAL
BOOLEAN
CB close travel time exceeded set value
OPERALM
BOOLEAN
Number of CB operations exceeds alarm limit
OPERLO
BOOLEAN
Number of CB operations exceeds lockout limit
CBLIFEAL
BOOLEAN
Remaining life of CB reduced to Life alarm level
MONALM
BOOLEAN
CB 'not operated for long time' alarm
IPOWALPH
BOOLEAN
Accum I^CurrExponent integr over CB open travel
time exceeds alarm limit
IPOWLOPH
BOOLEAN
Accum I^CurrExponent integr over CB open travel
time exceeds lockout limit
SPCHALM
BOOLEAN
Spring charging time has crossed the set value
GPRESALM
BOOLEAN
Pressure below alarm level
GPRESLO
BOOLEAN
Pressure below lockout level
16.4.5
Settings
Table 659:
SSCBR Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Off
On
-
-
Off
Operation Off / On
GlobalBaseSel
1 - 12
-
1
1
Selection of one of the Global Base Value
groups
PhSel
Phase L1
Phase L2
Phase L3
-
-
Phase L1
Phase selection
RatedOperCurr
100.00 - 5000.00
A
0.01
1000.00
Rated operating current of the breaker
OperNoRated
1 - 99999
-
1
10000
Number of operations possible at rated
current
RatedFltCurr
500.00 - 99999.99
A
0.01
5000.00
Rated fault current of the breaker
OperNoFault
1 - 10000
-
1
1000
Number of operations possible at rated
fault current
tTrOpenAlm
0.000 - 0.200
s
0.001
0.040
Alarm level for open travel time
tTrCloseAlm
0.000 - 0.200
s
0.001
0.040
Alarm level for close travel time
OperAlmLevel
0 - 9999
-
1
200
Alarm level for number of operations
OperLOLevel
0 - 9999
-
1
300
Lockout level for number of operations
AccSelCal
Aux Contact
Trip Signal
-
-
Trip Signal
Accumulated energy calculation selection
Table continues on next page
Section 16
1MRK502052-UEN B
Monitoring
898
Technical manual
Содержание Relion REG670
Страница 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Страница 2: ......
Страница 44: ...38 ...
Страница 58: ...52 ...
Страница 80: ...74 ...
Страница 106: ...100 ...
Страница 482: ...476 ...
Страница 548: ...542 ...
Страница 570: ...564 ...
Страница 600: ...594 ...
Страница 608: ...602 ...
Страница 630: ...624 ...
Страница 862: ...856 ...
Страница 1094: ...1088 ...
Страница 1226: ...1220 ...
Страница 1250: ...1244 ...
Страница 1297: ...1291 ...