7.9.9.6
Simplified logic diagram
Uinj
Rshunt
95% Stator earth fault protection
STTIPHIZ
REX060
REG670
1
I
U
u_i_sef
u_u_sef
X
S
a>b
a
b
K1
K2
U
UN> = 5%
t
tON=0.5s
95% Trip
un
Compare &
Evaluate
ZRef2
ZRef3
ZRef4
ZRef5
SELECT REFERENCE
3
8
2
4
5
6
7
9
IEC10000325-2-en.vsd
Measured
Z
Bare
Z
Inj
I
Inj
U
N
U
R
f
ZRef1
IEC10000325 V1 EN
Figure 143:
Simplified logic diagram for 100% stator earth fault protection
STTIPHIZ
1
The 100% stator earth fault protection function receives amplified injected voltage and current
via the REX060 unit as two voltage signals. (Voltage inputs in the REG670).
2
The phasor of injected voltage U
Inj
and phasor of injected current I
Inj
is calculated by using
special filter from raw samples. Observe that phasors are calculated for the injected
frequency.
3
The complex bare impedance is calculated from U
inj
/ I
inj
.
4, 5
The complex measured impedance is derived as Z
Measured
= Z
bare
*
k1 + k2.
6
The fault resistance (R
Fault
) is calculated from the complex measured impedance and a
selected complex reference.
7
Selection of one (out of maximum 5) Z
Ref
.
8
Fourier filter to derive the phasor of zero sequence voltage at fundamental frequency
9
The 95% stator earth fault zero sequence over voltage function must operate in parallel with
STTIPHIZ.
1MRK502052-UEN B
Section 7
Impedance protection
317
Technical manual
Содержание Relion REG670
Страница 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Страница 2: ......
Страница 44: ...38 ...
Страница 58: ...52 ...
Страница 80: ...74 ...
Страница 106: ...100 ...
Страница 482: ...476 ...
Страница 548: ...542 ...
Страница 570: ...564 ...
Страница 600: ...594 ...
Страница 608: ...602 ...
Страница 630: ...624 ...
Страница 862: ...856 ...
Страница 1094: ...1088 ...
Страница 1226: ...1220 ...
Страница 1250: ...1244 ...
Страница 1297: ...1291 ...