Figure 149:
Simplified offset mho characteristics for L1-L2 fault in zone 1
Criteria: Operation occurs if 90° ≤ β ≤ 270°.
In the above characteristics,
Z1Fwd
and
Z1Rev
are the forward and reverse reach
percentage values and
ImpedanceAng
is the characteristic angle provided for the zone
1 operation region.
1
1
Z Fwd
Z Fwd
ImpedanceAng
=
Ð
IECEQUATION14000025 V2 EN
(Equation 54)
1
1
Z Rev
Z rev ImpedanceAng
=
Ð
IECEQUATION14000026 V2 EN
(Equation 55)
Voltage and current phasors selected for phase-to-phase loops are:
Sl.No
Phase-to-phase loop
Voltage phasor
Current phasor
1
L1-L2
1 2
UL L
1 2
IL L
2
L2-L3
2 3
UL L
2 3
IL L
3
L3-L1
3 1
UL L
3 1
IL L
Operate time
The operate time delay for zone 1 can be provided using the setting
tZ1
.
7.10.7.2
Operation principle of zone 2
shows the function block diagram describing the functionality of zone 2.
Section 7
1MRK502052-UEN B
Impedance protection
326
Technical manual
Содержание Relion REG670
Страница 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Страница 2: ......
Страница 44: ...38 ...
Страница 58: ...52 ...
Страница 80: ...74 ...
Страница 106: ...100 ...
Страница 482: ...476 ...
Страница 548: ...542 ...
Страница 570: ...564 ...
Страница 600: ...594 ...
Страница 608: ...602 ...
Страница 630: ...624 ...
Страница 862: ...856 ...
Страница 1094: ...1088 ...
Страница 1226: ...1220 ...
Страница 1250: ...1244 ...
Страница 1297: ...1291 ...