Section 17
Metering
17.1
Pulse-counter logic PCFCNT
17.1.1
Identification
Function description
IEC 61850
identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Pulse-counter logic
PCFCNT
S00947 V1 EN
-
17.1.2
Functionality
Pulse-counter logic (PCFCNT) function counts externally generated binary pulses,
for instance pulses coming from an external energy meter, for calculation of energy
consumption values. The pulses are captured by the binary input module and then read
by the PCFCNT function. A scaled service value is available over the station bus. The
special Binary input module with enhanced pulse counting capabilities must be
ordered to achieve this functionality.
17.1.3
Function block
PCFCNT
BLOCK
READ_VAL
BI_PULSE*
RS_CNT
INVALID
RESTART
BLOCKED
NEW_VAL
SCAL_VAL
IEC14000043-1-en.vsd
IEC09000335 V3 EN
Figure 453:
PCFCNT function block
1MRK502052-UEN B
Section 17
Metering
981
Technical manual