14.10.5
Settings
Table 486:
SINGLECMD Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Off
Steady
Pulsed
-
-
Off
Operation Off / On
14.10.6
Operation principle
Single command, 16 signals (SINGLECMD) function has 16 binary output signals.
The outputs can be individually controlled from a substation automation system or
from the local HMI. Each output signal can be given a name with a maximum of 13
characters in PCM600.
The output signals can be of the types Off, Steady, or Pulse. This configuration setting
is done via the local HMI or PCM600 and is common for the whole function block.
The length of the output pulses are 100 ms. In steady mode, SINGLECMD function
has a memory to remember the output values at power interruption of the IED. Also
a BLOCK input is available used to block the updating of the outputs.
The output signals, OUT1 to OUT16, are available for configuration to built-in
functions or via the configuration logic circuits to the binary outputs of the IED.
Section 14
1MRK502052-UEN B
Control
790
Technical manual
Содержание Relion REG670
Страница 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Страница 2: ......
Страница 44: ...38 ...
Страница 58: ...52 ...
Страница 80: ...74 ...
Страница 106: ...100 ...
Страница 482: ...476 ...
Страница 548: ...542 ...
Страница 570: ...564 ...
Страница 600: ...594 ...
Страница 608: ...602 ...
Страница 630: ...624 ...
Страница 862: ...856 ...
Страница 1094: ...1088 ...
Страница 1226: ...1220 ...
Страница 1250: ...1244 ...
Страница 1297: ...1291 ...