16.1.5
Settings
The available setting parameters of the measurement function (MMXU, MSQI) are
depending on the actual hardware (TRM) and the logic configuration made in
PCM600.
These six functions are not handled as a group, so parameter settings are only available
in the first setting group.
The following terms are used in the Unit and Description columns:
•
UBase: Base voltage in primary kV. This voltage is used as reference for voltage
setting. It can be suitable to set this parameter to the rated primary voltage
supervised object.
•
IBase: Base current in primary A. This current is used as reference for current
setting. It can be suitable to set this parameter to the rated primary current of the
supervised object.
•
SBase: Base setting for power values in MVA.
Table 625:
CVMMXN Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
SLowLim
0.0 - 2000.0
%SB
0.1
80.0
Low limit in % of SBase
SLowLowLim
0.0 - 2000.0
%SB
0.1
60.0
Low Low limit in % of SBase
SMin
0.0 - 2000.0
%SB
0.1
50.0
Minimum value in % of SBase
SMax
0.0 - 2000.0
%SB
0.1
200.0
Maximum value in % of SBase
SRepTyp
Cyclic
Dead band
Int deadband
-
-
Cyclic
Reporting type
PMin
-2000.0 - 2000.0
%SB
0.1
-200.0
Minimum value in % of SBase
PMax
-2000.0 - 2000.0
%SB
0.1
200.0
Maximum value in % of SBase
PRepTyp
Cyclic
Dead band
Int deadband
-
-
Cyclic
Reporting type
QMin
-2000.0 - 2000.0
%SB
0.1
-200.0
Minimum value in % of SBase
QMax
-2000.0 - 2000.0
%SB
0.1
200.0
Maximum value in % of SBase
QRepTyp
Cyclic
Dead band
Int deadband
-
-
Cyclic
Reporting type
PFMin
-1.000 - 1.000
-
0.001
-1.000
Minimum value
PFMax
-1.000 - 1.000
-
0.001
1.000
Maximum value
PFRepTyp
Cyclic
Dead band
Int deadband
-
-
Cyclic
Reporting type
UMin
0.0 - 200.0
%UB
0.1
50.0
Minimum value in % of UBase
UMax
0.0 - 200.0
%UB
0.1
200.0
Maximum value in % of UBase
Table continues on next page
Section 16
1MRK502052-UEN B
Monitoring
864
Technical manual
Содержание Relion REG670
Страница 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Страница 2: ......
Страница 44: ...38 ...
Страница 58: ...52 ...
Страница 80: ...74 ...
Страница 106: ...100 ...
Страница 482: ...476 ...
Страница 548: ...542 ...
Страница 570: ...564 ...
Страница 600: ...594 ...
Страница 608: ...602 ...
Страница 630: ...624 ...
Страница 862: ...856 ...
Страница 1094: ...1088 ...
Страница 1226: ...1220 ...
Страница 1250: ...1244 ...
Страница 1297: ...1291 ...