From I/O
switchLR
TRU
E
FALS
E
Local= Operation at
switch yard level
Remote= Operation at
IED or higher level
en05000096.vsd
IEC05000096 V1 EN
Figure 341:
Local/Remote switch
Blocking principles
SXCBR includes several blocking principles. The basic principle for all blocking
signals is that they will affect commands from all other clients for example, switch
controller, protection functions and autoreclosure.
The blocking possibilities are:
•
Block/deblock for open command. It is used to block operation for open
command.
•
Block/deblock for close command. It is used to block operation for close
command.
•
Update block/deblock of positions. It is used to block the updating of position
values. Other signals related to the position will be reset.
•
Blocking of function, BLOCK. If BLOCK signal is set, it means that the function
is active, but no outputs are generated, no reporting, control commands are
rejected and functional and configuration data is visible.
The above blocking outputs are stored in a non-volatile memory.
Substitution
The substitution part in SXCBR is used for manual set of the position and quality of
the switch. The typical use of substitution is that an operator enters a manual value
because that the real process value is erroneous for some reason. SXCBR will then use
the manually entered value instead of the value for positions determined by the
process.
It is always possible to make a substitution, independently of the
position indication and the status information of the I/O board. When
substitution is enabled, the other signals related to the position follow
the substituted position. The substituted values are stored in a non-
volatile memory. If the function is blocked or blocked for update when
the substitution is released, the position value is kept the same as the
last substitution value, but the quality is changed to "questionable, old
data", indicating that the value is old and not reliable.
Section 14
1MRK502052-UEN B
Control
726
Technical manual
Содержание Relion REG670
Страница 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Страница 2: ......
Страница 44: ...38 ...
Страница 58: ...52 ...
Страница 80: ...74 ...
Страница 106: ...100 ...
Страница 482: ...476 ...
Страница 548: ...542 ...
Страница 570: ...564 ...
Страница 600: ...594 ...
Страница 608: ...602 ...
Страница 630: ...624 ...
Страница 862: ...856 ...
Страница 1094: ...1088 ...
Страница 1226: ...1220 ...
Страница 1250: ...1244 ...
Страница 1297: ...1291 ...