Function
Range or value
Accuracy
Active power, P
0.1 x U
r
< U < 1.5 x U
r
0.2 x I
r
< I < 4.0 x I
r
± 1.0% of S
r
at S ≤ S
r
± 1.0% of S at S > S
r
Conditions:
0.8 x U
r
< U < 1.2 U
r
0.2 x I
r
< I < 1.2 I
r
Reactive power, Q
0.1 x U
r
< U < 1.5 x U
r
0.2 x I
r
< I < 4.0 x I
r
Apparent power, S
0.1 x U
r
< U < 1.5 x U
r
0.2 x I
r
< I < 4.0 x I
r
Power factor, cos (φ)
0.1 x U
r
< U < 1.5 x U
r
0.2 x I
r
< I < 4.0 x I
r
± 0.02
Table 644:
CMMXU technical data
Function
Range or value
Accuracy
Current at symmetrical load
(0.1-4.0) × I
r
± 0.3% of I
r
at I ≤ 0.5 × I
r
± 0.3% of I at I > 0.5 × I
r
Phase angle at symmetrical load
(0.1-4.0) × I
r
± 1.0° at 0.1 × I
r
< I ≤ 0.5 × I
r
± 0.5° at 0.5 × I
r
< I ≤ 4.0 × I
r
Table 645:
VMMXU technical data
Function
Range or value
Accuracy
Voltage
(10 to 300) V
± 0.5% of U at U ≤ 50 V
± 0.2% of U at U > 50 V
Phase angle
(10 to 300) V
± 0.5° at U ≤ 50 V
± 0.2° at U > 50 V
Table 646:
CMSQI technical data
Function
Range or value
Accuracy
Current positive sequence, I1
Three phase settings
(0.1–4.0) × I
r
±
0.3% of I
r
at I ≤ 0.5 × I
r
±
0.3% of I at I > 0.5 × I
r
Current zero sequence, 3I0
Three phase settings
(0.1–1.0) × I
r
±
0.3% of I
r
at I ≤ 0.5 × I
r
±
0.3% of I at I > 0.5 × I
r
Current negative sequence, I2
Three phase settings
(0.1–1.0) × I
r
±
0.3% of I
r
at I ≤ 0.5 × I
r
±
0.3% of I at I > 0.5 × I
r
Phase angle
(0.1–4.0) × I
r
±
1.0° at 0.1 × I
r
< I ≤ 0.5 × I
r
±
0.5° at 0.5 × I
r
< I ≤ 4.0 × I
r
1MRK502052-UEN B
Section 16
Monitoring
889
Technical manual
Содержание Relion REG670
Страница 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Страница 2: ......
Страница 44: ...38 ...
Страница 58: ...52 ...
Страница 80: ...74 ...
Страница 106: ...100 ...
Страница 482: ...476 ...
Страница 548: ...542 ...
Страница 570: ...564 ...
Страница 600: ...594 ...
Страница 608: ...602 ...
Страница 630: ...624 ...
Страница 862: ...856 ...
Страница 1094: ...1088 ...
Страница 1226: ...1220 ...
Страница 1250: ...1244 ...
Страница 1297: ...1291 ...