Name
Values (Range)
Unit
Step
Default
Description
UL12LowLowLim
0.0 - 200.0
%UB
0.1
60.0
Low Low limit in % of UBase
UAmpComp100
-10.000 - 10.000
%
0.001
0.000
Amplitude factor to calibrate voltage at
100% of Ur
UL12Min
0.0 - 200.0
%UB
0.1
50.0
Minimum value in in % of UBase
UL12LimHys
0.000 - 100.000
%
0.001
5.000
Hysteresis value in % of range and is
common for all limits
UL23HiHiLim
0.0 - 200.0
%UB
0.1
150.0
High High limit in % of UBase
UL23HiLim
0.0 - 200.0
%UB
0.1
120.0
High limit in % of UBase
UL23LowLim
0.0 - 200.0
%UB
0.1
80.0
Low limit in % of UBase
UL23LowLowLim
0.0 - 200.0
%UB
0.1
60.0
Low Low limit in % of UBase
UL23Min
0.0 - 200.0
%UB
0.1
50.0
Minimum value in % of UBase
UL23LimHys
0.000 - 100.000
%
0.001
5.000
Hysteresis value in % of range and is
common for all limits
UL31HiHiLim
0.0 - 200.0
%UB
0.1
150.0
High High limit in % of UBase
UL31HiLim
0.0 - 200.0
%UB
0.1
120.0
High limit in % of UBase
UL31LowLim
0.0 - 200.0
%UB
0.1
80.0
Low limit in % of UBase
UL31LowLowLim
0.0 - 200.0
%UB
0.1
60.0
Low Low limit in % of UBase
UL31Min
0.0 - 200.0
%UB
0.1
50.0
Minimum value in % of UBase
UL31LimHys
0.000 - 100.000
%
0.001
5.000
Hysteresis value in % of range and is
common for all limits
Table 631:
CMSQI Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
3I0DbRepInt
1 - 300
Type
1
10
Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
3I0ZeroDb
0 - 100000
m%
1
1
Zero point clamping
3I0Min
0.0 - 500.0
%IB
0.1
50.0
Minimum value in % of IBase
3I0Max
0.0 - 500.0
%IB
0.1
200.0
Maximum value in % of IBase
3I0RepTyp
Cyclic
Dead band
Int deadband
-
-
Cyclic
Reporting type
GlobalBaseSel
1 - 12
-
1
1
Selection of one of the Global Base Value
groups
3I0LimHys
0.000 - 100.000
%
0.001
5.000
Hysteresis value in % of range and is
common for all limits
3I0AngDbRepInt
1 - 300
Type
1
10
Cycl: Report interval (s), Db: In % of
range, Int Db: In %s
Operation
Off
On
-
-
Off
Operation Mode On / Off
3I0AngMin
-180.000 - 180.000
Deg
0.001
-180.000
Minimum value
3I0AngMax
-180.000 - 180.000
Deg
0.001
180.000
Maximum value
3I0AngRepTyp
Cyclic
Dead band
Int deadband
-
-
Cyclic
Reporting type
Table continues on next page
Section 16
1MRK502052-UEN B
Monitoring
870
Technical manual
Содержание Relion REG670
Страница 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Страница 2: ......
Страница 44: ...38 ...
Страница 58: ...52 ...
Страница 80: ...74 ...
Страница 106: ...100 ...
Страница 482: ...476 ...
Страница 548: ...542 ...
Страница 570: ...564 ...
Страница 600: ...594 ...
Страница 608: ...602 ...
Страница 630: ...624 ...
Страница 862: ...856 ...
Страница 1094: ...1088 ...
Страница 1226: ...1220 ...
Страница 1250: ...1244 ...
Страница 1297: ...1291 ...