If the two negative sequence currents flow in opposite directions, the fault is
external.
•
Under external fault condition, the relative angle is theoretically equal to 180°.
Under internal fault condition, the angle is ideally 0°, but due to possible different
negative-sequence impedance angles on both sides of the internal fault, it may
differ somewhat from 0°.
The setting
NegSeqROA
, as shown in figure
, represents the so called Relay Operate
Angle, which determines the boundary between the internal and external fault regions.
It can be selected in the range ±30° to ±90°, with a step of 1°. The default value is ±60°.
The default setting, ±60°, favors somewhat security in comparison to dependability.
Magnitudes of both negative-sequence currents which are to be compared as to their
phase positions in the complex plane must be high enough so that one can be sure that
they are due to a fault. The limit value
IMinNegSeq
is settable in the range [0.02 – 0.20]
of the protected generator rated current. Adaptability is introduced if the bias current
is higher than 150 % rated current. Adaptability is introduced 10 ms after this limit of
150 % rated current has been crossed so that the internal/external discriminator is
given the time to detect correctly a fault before an eventual CT saturation sets in. The
threshold
IMinNegSeq
is dynamically increased by 4 % of the bias current, in case of
internal faults, and by 8 % of the bias current in case of external faults. Only if
magnitudes of both currents are above the limit
IMinNegSeq
, the angle between the
two currents is calculated. If any of the two currents is too small, no decision is taken
regarding the relative position of the fault, and this feature then remains inactive rather
than to produce a wrong decision. The relative angle is then assigned the value of 120°
(2.094 radians). If this value persists, then this is an indication that no directional
comparison has been made. Neither internal, nor external fault (disturbance) is
declared in this case.
1MRK502052-UEN B
Section 6
Differential protection
157
Technical manual
Содержание Relion REG670
Страница 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Страница 2: ......
Страница 44: ...38 ...
Страница 58: ...52 ...
Страница 80: ...74 ...
Страница 106: ...100 ...
Страница 482: ...476 ...
Страница 548: ...542 ...
Страница 570: ...564 ...
Страница 600: ...594 ...
Страница 608: ...602 ...
Страница 630: ...624 ...
Страница 862: ...856 ...
Страница 1094: ...1088 ...
Страница 1226: ...1220 ...
Страница 1250: ...1244 ...
Страница 1297: ...1291 ...