18.14
Security events on protocols SECALARM
18.14.1
Security alarm SECALARM
18.14.1.1
Signals
Table 812:
SECALARM Output signals
Name
Type
Description
EVENTID
INTEGER
EventId of the generated security event
SEQNUMBER
INTEGER
Sequence number of the generated security event
18.14.1.2
Settings
Table 813:
SECALARM Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
Operation
Off
On
-
-
On
Operation On/Off
18.15
Activity logging parameters ACTIVLOG
18.15.1
Activity logging ACTIVLOG
ACTIVLOG contains all settings for activity logging.
There can be 6 external log servers to send syslog events to. Each server can be
configured with IP address; IP port number and protocol format. The format can be
either syslog (RFC 5424) or Common Event Format (CEF) from ArcSight.
18.15.2
Settings
Table 814:
ACTIVLOG Non group settings (basic)
Name
Values (Range)
Unit
Step
Default
Description
ExtLogSrv1Type
Off
SYSLOG UDP/IP
SYSLOG TCP/IP
CEF TCP/IP
-
-
Off
External log server 1 type
ExtLogSrv1Port
1 - 65535
-
1
514
External log server 1 port number
ExtLogSrv1IP
0 - 18
IP
Address
1
127.0.0.1
External log server 1 IP-address
ExtLogSrv2Type
Off
SYSLOG UDP/IP
SYSLOG TCP/IP
CEF TCP/IP
-
-
Off
External log server 2 type
Table continues on next page
1MRK502052-UEN B
Section 18
Station communication
1077
Technical manual
Содержание Relion REG670
Страница 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Страница 2: ......
Страница 44: ...38 ...
Страница 58: ...52 ...
Страница 80: ...74 ...
Страница 106: ...100 ...
Страница 482: ...476 ...
Страница 548: ...542 ...
Страница 570: ...564 ...
Страница 600: ...594 ...
Страница 608: ...602 ...
Страница 630: ...624 ...
Страница 862: ...856 ...
Страница 1094: ...1088 ...
Страница 1226: ...1220 ...
Страница 1250: ...1244 ...
Страница 1297: ...1291 ...