(
)
- × ×
-
= ×
>
æ
ö
æ
ö
ç
÷
ç
÷
è
ø
è
ø
p
op
i
t
B k
C
A k
in
EQUATION1190 V1 EN
(Equation 159)
where:
t
op
is the operating time of the protection
The time elapsed to the moment of trip is reached when the integral fulfils according
to equation
, in addition to the constant time delay:
0
-
×
³ ×
>
æ
ö
æ
ö
ç
÷
ç
÷
è
ø
è
ø
ò
p
t
i
C
dt
A k
in
EQUATION1191 V1 EN
(Equation 160)
For the numerical protection the sum below must fulfil the equation for trip.
1
( )
=
D ×
-
³ ×
>
æ
ö
æ
ö
ç
÷
ç
÷
è
ø
è
ø
å
p
n
j
i j
t
C
A k
in
EQUATION1192 V1 EN
(Equation 161)
where:
j = 1
is the first protection execution cycle when a fault has been
detected, that is, when
1
i
in
>
>
EQUATION1193 V1 EN
D
t
is the time interval between two consecutive executions of the
protection algorithm,
n
is the number of the execution of the algorithm when the trip time
equation is fulfilled, that is, when a trip is given and
i (j)
is the fault current at time j
For inverse time operation, the inverse time characteristic is selectable. Both the IEC
and ANSI/IEEE standardized inverse time characteristics are supported.
For the IEC curves there is also a setting of the minimum time-lag of operation, see
figure
1MRK502052-UEN B
Section 25
Inverse time characteristics
1249
Technical manual
Содержание Relion REG670
Страница 1: ...Relion 670 series Generator protection REG670 2 0 IEC Technical manual ...
Страница 2: ......
Страница 44: ...38 ...
Страница 58: ...52 ...
Страница 80: ...74 ...
Страница 106: ...100 ...
Страница 482: ...476 ...
Страница 548: ...542 ...
Страница 570: ...564 ...
Страница 600: ...594 ...
Страница 608: ...602 ...
Страница 630: ...624 ...
Страница 862: ...856 ...
Страница 1094: ...1088 ...
Страница 1226: ...1220 ...
Страница 1250: ...1244 ...
Страница 1297: ...1291 ...