What to do
Cause
Event name /
Aux. code
Code
(hex)
Check the external device.
Fault in external device 2.
External fault
2
9082
Check setting of parameter
.
Check the external device.
Fault in external device 3.
External fault
3
9083
Check setting of parameter
.
Check the external device.
Fault in external device 4.
External fault
4
9084
Check setting of parameter
Check the external device.
Fault in external device 5.
External fault
5
9085
Check setting of parameter
.
Informative warning. (See parameter
.)
Current offset and gain measurement
calibration will occur at next start.
Current
calibration
A2A1
Check there are no power factor
correction capacitors or surge
absorbers in motor cable.
Drive has detected load unbalance
typically due to earth fault in motor or
motor cable.
Earth leakage
A2B3
Check for an earth fault in motor or
motor cables by measuring the
insulation resistances of motor and
motor cable.
Try running the motor in scalar control
mode if allowed. (See parameter
99.4
Motor control mode.)
If no earth fault can be detected,
contact your local ABB representative.
Check motor and motor cable for
cabling errors.
Short-circuit in motor cable(s) or
motor.
Short circuit
A2B4
Check there are no power factor
correction capacitors or surge
absorbers in motor cable.
Check motor cable.
Excessive IGBT junction to case
temperature. This warning protects
IGBT overload
A2BA
Check ambient conditions.
the IGBT(s) and can be activated by a
short circuit in the motor cable.
Check air flow and fan operation.
Check heatsink fins for dust pick-up.
Check motor power against drive
power.
Check the supply voltage setting
(parameter
). Note
Intermediate circuit DC voltage too
high (when the drive is stopped).
DC link
overvoltage
A3A1
that the wrong setting of the
parameter may cause the motor to
rush uncontrollably, or may overload
the brake chopper or resistor.
Check the supply voltage.
If the problem persists, contact your
local ABB representative.
Check the supply voltage setting
(parameter
). Note
Intermediate circuit DC voltage too
low (when the drive is stopped).
DC link
undervoltage
A3A2
that the wrong setting of the
parameter may cause the motor to
rush uncontrollably, or may overload
the brake chopper or resistor.
Fault tracing 671
Содержание ACS880 Series
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 ESP control program option N5600 Firmware manual ...
Страница 2: ......
Страница 4: ......
Страница 16: ...16 ...
Страница 22: ...22 ...
Страница 24: ...24 ...
Страница 44: ...44 ...
Страница 66: ...66 ...
Страница 148: ...148 ...
Страница 167: ...Fieldbus control macro This application macro is not supported by the current firmware version Application macros 167 ...
Страница 168: ...168 ...
Страница 704: ...704 ...
Страница 728: ...728 ...
Страница 742: ...742 ...
Страница 762: ...762 ...