Def / Type
FbEq 16b / 32b
Description
Name / Range /
Selection
No.
1 = Channel CH9 is routed to a local power unit
b8
1 = Channel CH10 is routed to a local power unit
b9
1 = Channel CH11 is routed to a local power unit
b10
1 = Channel CH12 is routed to a local power unit
b11
Reserved
b12…15
1 = 1
0000h…FFFFh
- / uint16
Specifies hardware-related options that require
differentiated parameter defaults. Activating a bit in
this parameter makes the necessary changes in other
parameters. For example, activating an emergency stop
option reserves a digital input. In many cases, the
differentiated parameters will also be write-protected.
This parameter, as well as the changes in other
parameters implemented by it, are not affected by a
parameter restore.
WARNING! After switching any bits in this word,
recheck the values of the affected parameters.
Note: This parameter cannot be changed while the
drive is running.
*See section
Control of a supply unit (LSU).
HW options word 1
95.20
0 = 50 Hz; 1 = 60 Hz. Affects
,
,
,
,
,
,
Supply frequency 60
Hz
b0
1 = Emergency stop, Category 0, without FSO module.
Affects
,
,
.
Emergency stop Cat
0
b1
1 = Emergency stop, Category 1, without FSO module.
Affects
,
Emergency stop Cat
1
b2
1 = Control of cabinet cooling fan (used only with
specific ACS880-07 hardware). Affects
,
,
.
RO2 for -07 cabinet
cooling fan
b3
1 = Control unit powered externally. Affects
(Only
visible with a ZCU control unit)
Externally powered
control unit
b4
1 = DC switch monitoring active. Affects
,
.
(Only visible with a ZCU control unit)
DC supply switch
b5
1 = Motor fan control active. Affects
,
,
.
DOL motor switch
b6
Reserved
b7
1 = Service switch or PTC/Pt100 relay connected.
Affects
Service switch or
PTC/Pt100 relay
b8
1 = Output contactor present. Affects
.
Output contactor
b9
1 = Status (eg. thermal) switches connected to DIIL
input. Affects
.
Brake resistor, sine
filter, IP54 fan
b10
598 Parameters
Содержание ACS880 Series
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 ESP control program option N5600 Firmware manual ...
Страница 2: ......
Страница 4: ......
Страница 16: ...16 ...
Страница 22: ...22 ...
Страница 24: ...24 ...
Страница 44: ...44 ...
Страница 66: ...66 ...
Страница 148: ...148 ...
Страница 167: ...Fieldbus control macro This application macro is not supported by the current firmware version Application macros 167 ...
Страница 168: ...168 ...
Страница 704: ...704 ...
Страница 728: ...728 ...
Страница 742: ...742 ...
Страница 762: ...762 ...