Def / Type
FbEq 16b / 32b
Description
Name / Range /
Selection
No.
0.00 s / real32
(Visible when
=
Defines the deactivation delay for digital input/output
DIO2.
See parameter
.
DIO2 OFF delay
14.18
10 = 1 s / 100 = 1 s
Deactivation delay for DIO2.
0.00 ... 3000.00 s
No action / uint16
(Visible when
=
)
Selects how the drive reacts when an analog input
signal moves out of the minimum and/or maximum
limits specified for the input.
The inputs and the limits to be observed are selected
by parameter
AI supervision
function
14.19
0
No action taken.
No action
1
Drive trips on
.
Fault
2
Drive generates an
warning.
Warning
3
Drive generates a warning (
) and freezes the speed (or frequency) to the
level the drive was operating at. The speed/frequency
is determined on the basis of actual speed using
850 ms low-pass filtering.
WARNING!
Make sure that it is safe to continue operation
in case of a communication break.
Last speed
4
Drive generates a warning (
) and sets the speed to the speed defined by
parameter
(or
when frequency reference is being used).
WARNING!
Make sure that it is safe to continue operation
in case of a communication break.
Speed ref safe
Input / uint16
(Visible when
=
Selects whether DIO3 of the extension module is used
as a digital input or output.
DIO3 function
14.19
0
DIO3 is used as a digital output.
Output
1
DIO3 is used as a digital input.
Input
- / uint16
(Visible when
=
)
Specifies the analog input limits to be supervised. See
parameter
Note: The number of active bits in this parameter
depends on the number of inputs on the extension
module.
AI supervision
selection
14.20
1 = Minimum limit supervision of AI1 active.
AI1 < MIN
b0
1 = Maximum limit supervision of AI1 active.
AI1 > MAX
b1
1 = Minimum limit supervision of AI2 active.
AI2 < MIN
b2
Parameters 243
Содержание ACS880 Series
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 ESP control program option N5600 Firmware manual ...
Страница 2: ......
Страница 4: ......
Страница 16: ...16 ...
Страница 22: ...22 ...
Страница 24: ...24 ...
Страница 44: ...44 ...
Страница 66: ...66 ...
Страница 148: ...148 ...
Страница 167: ...Fieldbus control macro This application macro is not supported by the current firmware version Application macros 167 ...
Страница 168: ...168 ...
Страница 704: ...704 ...
Страница 728: ...728 ...
Страница 742: ...742 ...
Страница 762: ...762 ...