PID control macro
The PID control macro is suitable for process control applications, for example
closed-loop pressure, level or flow control systems such as
•
pressure boost pumps of municipal water supply systems
•
level-controlling pumps of water reservoirs
•
pressure boost pumps of district heating systems
•
material flow control on a conveyor line.
The process reference signal is connected to analog input AI1 and the process
feedback signal to AI2. Alternatively, a direct speed reference can be given to the
drive through AI1. Then the PID controller is bypassed and the drive no longer
controls the process variable.
Selection between direct speed control (control location EXT1) and process variable
control (EXT2) is done through digital input DI3.
The stop/start signals for EXT1 and EXT2 are connected to DI1 and DI6 respectively.
A constant speed (by default, 300 rpm) can be activated through DI4.
Note: When commissioning the PID loop, it is useful to run the motor in speed
control first using EXT1; this allows testing of the PID feedback polarity and scaling.
Once the feedback has been proven, the PID loop can be “closed” by switching to
EXT2.
■
Default parameter settings for the PID control macro
Below is a listing of default parameter values that differ from those listed for the
Factory macro in
.
Hand/Auto macro default
Parameter
4.000
Application macros 155
Содержание ACS880 Series
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 ESP control program option N5600 Firmware manual ...
Страница 2: ......
Страница 4: ......
Страница 16: ...16 ...
Страница 22: ...22 ...
Страница 24: ...24 ...
Страница 44: ...44 ...
Страница 66: ...66 ...
Страница 148: ...148 ...
Страница 167: ...Fieldbus control macro This application macro is not supported by the current firmware version Application macros 167 ...
Страница 168: ...168 ...
Страница 704: ...704 ...
Страница 728: ...728 ...
Страница 742: ...742 ...
Страница 762: ...762 ...