Def / Type
FbEq 16b / 32b
Description
Name / Range /
Selection
No.
1 = Constant speed or frequency 3 selected
Constant speed 3
b2
1 = Constant speed or frequency 4 selected
Constant speed 4
b3
1 = Constant speed or frequency 5 selected
Constant speed 5
b4
1 = Constant speed or frequency 6 selected
Constant speed 6
b5
1 = Constant speed or frequency 7 selected
Constant speed 7
b6
Reserved
b7…15
1 = 1
0000h…FFFFh
- / uint16
Drive status word 3.
This parameter is read-only.
Drive status word 3
6.21
1 = DC hold is active (see par.
)
DC hold active
b0
1 = Post-magnetizing is active (see par.
)
Post-magnetizing
active
b1
1 = Motor pre-heating is active (see par.
Motor pre-heating
active
b2
Reserved
Smooth start active
b3
1 = Rotor position has been determined (autophasing
not needed). See section
.
Rotor position
known
b4
Brake chopper active. See section
Brake chopper
active
b5
Motor temperature
estimation active
b6
Reserved
b7…15
1 = 1
0000h…FFFFh
- / uint16
Drive inhibit status word 2. This word specifies the
source of the inhibiting condition that is preventing
the drive from starting. After the condition is removed,
the start command must be cycled. See bit-specific
notes.
See also parameter
6.18 Start inhibit status word
, and
, bit 1.
This parameter is read-only.
Note:
•
If bit 1 of
is still set after
the removal of the inhibiting condition, and edge
triggering is selected for the active external
control location, a fresh rising-edge start signal
is required. See parameters
,
and
.
•
If bit 1 of
is still set after
the removal of the inhibiting condition, a fresh
rising-edge start signal is required.
Drive inhibit status
word 2
6.25
1 = A follower is preventing the master from starting.
Follower drive
b0
1 = The application program is preventing the drive
from starting.
Application
b1
196 Parameters
Содержание ACS880 Series
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 ESP control program option N5600 Firmware manual ...
Страница 2: ......
Страница 4: ......
Страница 16: ...16 ...
Страница 22: ...22 ...