Def / Type
FbEq 16b / 32b
Description
Name / Range /
Selection
No.
2
Stop according to torque limits (parameters
and
).
Torque limit
Ramp stop (Off1);
Coast stop (Off2)
(95.20 b1); Eme ramp
stop (Off3) (95.20 b2)
/ uint16
Selects the way the motor is stopped when an
emergency stop command is received.
The source of the emergency stop signal is selected by
parameter
.
Emergency stop
mode
21.4
0
With the drive running:
•
1 = Normal operation.
•
0 = Normal stop along the standard deceleration
ramp defined for the particular reference type (see
section
). After the
drive has stopped, it can be restarted by removing
the emergency stop signal and switching the start
signal from 0 to 1.
With the drive stopped:
•
1 = Starting allowed.
•
0 = Starting not allowed.
Ramp stop (Off1)
1
With the drive running:
•
1 = Normal operation.
•
0 = Stop by coasting. The drive can be restarted
by restoring the start interlock signal and
switching the start signal from 0 to 1.
With the drive stopped:
•
1 = Starting allowed.
•
0 = Starting not allowed.
Coast stop (Off2)
2
With the drive running:
•
1 = Normal operation.
•
0 = Stop by ramping along emergency stop ramp
defined by parameter
After the drive has stopped, it can be restarted by
removing the emergency stop signal and
switching the start signal from 0 to 1.
With the drive stopped:
•
1 = Starting allowed.
•
0 = Starting not allowed.
Eme ramp stop
(Off3)
292 Parameters
Содержание ACS880 Series
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 ESP control program option N5600 Firmware manual ...
Страница 2: ......
Страница 4: ......
Страница 16: ...16 ...
Страница 22: ...22 ...
Страница 24: ...24 ...
Страница 44: ...44 ...
Страница 66: ...66 ...
Страница 148: ...148 ...
Страница 167: ...Fieldbus control macro This application macro is not supported by the current firmware version Application macros 167 ...
Страница 168: ...168 ...
Страница 704: ...704 ...
Страница 728: ...728 ...
Страница 742: ...742 ...
Страница 762: ...762 ...