What to do
Cause
Event name /
Aux. code
Code
(hex)
See
High temperature difference between
the IGBTs of different phases. The
amount of available temperatures
depends on the frame size.
Excess
temperature
difference
4E04
Check the cooling of the cabinet, LCL
filter and auxiliary transformer.
Overtemperature detected either in
cabinet, LCL filter or auxiliary
transformer.
Cabinet or
LCL
overtemperature
4E06
Check the fan operation and
connection.
Replace the fan if faulty.
An auxiliary cooling fan is stuck or
disconnected.
Auxiliary fan
broken
5E01
Cycle the power to the supply unit. If
the control unit is externally powered,
reboot the control unit (using
parameter
) or by cycling its power.
If the problem persists, contact your
local ABB representative.
The hardware of the supply unit does
not match the information stored in
the memory unit. This may occur eg,
after a firmware update or memory
unit replacement.
Rating ID
mismatch
5E05
Check main contactor / main breaker
control circuit wiring.
Check the status of other switches
connected to contactor control circuit.
See the delivery-specific circuit
diagrams.
Check main contactor operating
voltage level (should be 230 V).
Check digital input DI3 connections.
Control program does not receive
main contactor on (1)
acknowledgement through digital
input even control program has closed
the contactor control circuit with relay
output.
Main contactor / main breaker is not
functioning properly, or there is a
loose / bad connection.
Main
contactor
Fault
5E06
Monitor possible network transients.
Synchronization to supply network has
failed.
Synchronization
fault
6E19
Contact your local ABB representative.
Rating ID load error.
Rating ID fault
6E1A
Check the line-converter control
program. Record the auxiliary codes
of all active licensing faults and
contact your product vendor for
further instructions.
This fault requires a reboot of the
control unit either by switching the
power off and on, or using parameter
.
8201: Contact your product vendor for
further instructions.
There are two types of licenses being
used in ACS880 drives:
licenses that need to be found from
the unit which allow the firmware to
be executed, and licenses that prevent
the firmware from running. The license
is indicated by the value of the
auxiliary code field. The license is
Nxxxx, where xxxx is indicated by the
4-digit value of the auxiliary code field.
8201: A restrictive license is found
from the unit. The firmware on this
inverter unit cannot be executed
because a Low harmonic license is
found from the unit. This unit is meant
to be used with IGBT supply control
program (2Q) only.
Licensing
fault
6E1F
Check PC tool or control panel
connection.
Check control panel connector.
Replace control panel in mounting
platform.
Control panel or PC tool selected as
active control location has ceased
communicating.
Panel loss
7E01
702 Fault tracing
Содержание ACS880 Series
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 ESP control program option N5600 Firmware manual ...
Страница 2: ......
Страница 4: ......
Страница 16: ...16 ...
Страница 22: ...22 ...
Страница 24: ...24 ...
Страница 44: ...44 ...
Страница 66: ...66 ...
Страница 148: ...148 ...
Страница 167: ...Fieldbus control macro This application macro is not supported by the current firmware version Application macros 167 ...
Страница 168: ...168 ...
Страница 704: ...704 ...
Страница 728: ...728 ...
Страница 742: ...742 ...
Страница 762: ...762 ...