![ABB ACS880 Series Скачать руководство пользователя страница 534](http://html.mh-extra.com/html/abb/acs880-series/acs880-series_firmware-manual_2617534.webp)
Def / Type
FbEq 16b / 32b
Description
Name / Range /
Selection
No.
100 = 1 / 10 = 1
Process 1 max scale.
1.00 ... 3000000.00
1.00 %/Interval /
real32
Defines the process 1 reference change step.
Together with parameter
, the desired dynamics for the process 1
reference are defined.
Process 1 reference
change rate
76.38
100 = 1 %/Interval /
10 = 1 %/Interval
Process 1 reference change rate.
0.00 ... 100000.00
%/Interval
1.0 s / real32
Defines the process 1 reference step change interval
time.
Together with parameter
the desired dynamics for the process 1
reference are defined.
Process 1 ref step
interval
76.39
10 = 1 s / 1 = 1 s
Process 1 ref step interval.
0.0 ... 30000.0 s
1.000 / real32
Defines the proportional gain setting for the process
1 PI controller.
Process 1 control
P-gain
76.41
1000 = 1 / 100 = 1
Process 1 control P-gain.
0.000 ... 100000.000
100.0 s / real32
Defines the integration time setting for the process 1
PI controller.
Process 1 control
I-time
76.42
10 = 1 s / 10 = 1 s
Process 1 control I-time.
0.0 ... 1000000.0 s
- / unit16
Defines the source for the process 2 feedback signal.
See parameter
76.31 Process 1 control feedback src
.
Process 2 control
feedback src
76.51
- / real32
Defines the value for the process 2 reference set point.
See parameter
76.33 Process 1 control set point
.
Process 2 control set
point
76.53
- / real32
Defines the value for the process 2 feedback and
reference unit scaling.
See parameter
.
Process 2 max scale
76.55
1.00 %/Interval /
real32
Defines the process 2 reference change step.
Together with parameter
, it defines the desired dynamics for the process
2 reference.
Process 2 reference
change rate
76.58
10 = 1 %/Interval /
100 = 1 %/Interval
Process 2 reference change rate.
0.00 ... 100000.00
%/Interval
1.0 s / real32
Defines the process 2 reference step change interval
time.
Together with parameter
, the desired dynamics for the process 2
reference are defined.
Process 2 ref step
interval
76.59
1 = 1 s / 10 = 1 s
Process 2 ref step interval.
0.0 ... 30000.0 s
1.000 / real32
Defines the proportional gain setting for the process
2 PI controller.
Process 2 control
P-gain
76.61
100 = 1 / 1000 = 1
Process 2 control P-gain.
0.000 ... 100000.000
100.0 s / real32
Defines integration time setting for the process 2 PI
controller.
Process 2 control
I-time
76.62
10 = 1 s / 10 = 1 s
Process 2 control I-time.
0.0 ... 1000000.0 s
534 Parameters
Содержание ACS880 Series
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 ESP control program option N5600 Firmware manual ...
Страница 2: ......
Страница 4: ......
Страница 16: ...16 ...
Страница 22: ...22 ...
Страница 24: ...24 ...
Страница 44: ...44 ...
Страница 66: ...66 ...
Страница 148: ...148 ...
Страница 167: ...Fieldbus control macro This application macro is not supported by the current firmware version Application macros 167 ...
Страница 168: ...168 ...
Страница 704: ...704 ...
Страница 728: ...728 ...
Страница 742: ...742 ...
Страница 762: ...762 ...