What to do
Cause
Event name /
Aux. code
Code
(hex)
Insert a compatible, writable SD
card into the SD CARD slot of the
BCU control unit.
No SD card.
0
Insert a compatible, writable SD
card into the SD CARD slot of the
BCU control unit.
SD card write-protected.
1
Insert a compatible, writable SD
card into the SD CARD slot of the
BCU control unit.
SD card unreadable.
2
Check the supply voltage.
Power fail saving is requested too
frequently. Because of the limited
Power fail
saving
A685
saving interval, some of the requests
do not trigger the saving and power
fail data may be lost. This may be
caused by DC voltage oscillation.
Check that all necessary approved
(reference) checksums (
…
The calculated parameter checksum
does not match any enabled reference
checksum.
Checksum
mismatch
A686
are enabled in
.
Check the parameter configuration.
Using
enable a checksum parameter and
copy the actual checksum into that
parameter.
Contact your local ABB representative
for configuring the feature, or disable
the feature in
An action has been defined for a
parameter checksum mismatch but
the feature has not been configured.
Checksum
configuration
A687
See the
Drive customizer PC tool user’s
manual (3AUA0000104167 [English]).
Too much data in parameter mapping
table created in Drive customizer.
Parameter
map
configuration
A688
Check parameter scaling and format
in parameter mapping table. See the
Parameter value saturated eg. by the
scaling specified in parameter
Mapped
parameter
value cut
A689
Drive customizer PC tool user’s manual
(3AUA0000104167 [English]).
mapping table (created in Drive
customizer).
Check the auxiliary code. See actions
for each code below.
The motor parameters are set
incorrectly.
The drive is not dimensioned correctly.
Motor
nominal value
A6A4
Check the settings of the motor
configuration parameters in groups
98 and 99.
Slip frequency is too small.
1
Check that the drive is sized
correctly for the motor.
Check the settings of the motor
configuration parameters in groups
98 and 99.
Synchronous and nominal speeds
differ too much.
2
Check that the drive is sized
correctly for the motor.
Check the settings of the motor
configuration parameters in groups
98 and 99.
Nominal speed is higher than
synchronous speed with 1 pole pair.
3
Check that the drive is sized
correctly for the motor.
Fault tracing 677
Содержание ACS880 Series
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 ESP control program option N5600 Firmware manual ...
Страница 2: ......
Страница 4: ......
Страница 16: ...16 ...
Страница 22: ...22 ...
Страница 24: ...24 ...
Страница 44: ...44 ...
Страница 66: ...66 ...
Страница 148: ...148 ...
Страница 167: ...Fieldbus control macro This application macro is not supported by the current firmware version Application macros 167 ...
Страница 168: ...168 ...
Страница 704: ...704 ...
Страница 728: ...728 ...
Страница 742: ...742 ...
Страница 762: ...762 ...