What to do
Cause
Event name /
Aux. code
Code
(hex)
Check brake chopper and resistor (if
present).
Check deceleration time.
Use coast-to-stop function (if
applicable).
Retrofit drive with brake chopper and
brake resistor.
With parallel-connected modules,
check the auxiliary code (format XXXY
YYZZ).
“Y YY” specifies through which BCU
control unit channel the fault was
received.
Check supply cabling, fuses and
switchgear.
Intermediate circuit DC voltage is not
sufficient because of a missing supply
DC link
undervoltage
3220
With parallel-connected modules,
check the auxiliary code (format XXXY
YYZZ).
phase, blown fuse or fault in the
rectifier bridge.
“Y YY” specifies through which BCU
control unit channel the fault was
received.
Check the condition of the supply
(voltage, cabling, fuses, switchgear).
Automatic restart failed (see section
).
Standby
timeout
3280
Check the auxiliary code (format XXXY
YYZZ). “XXX” specifies the source of
Difference in DC voltages between
parallel-connected inverter modules.
DC voltage
difference
3291
the first error (see “YYY”). “YYY”
specifies the module through which
BCU control unit channel the fault was
received (1: Channel 1, 2: Channel 2, 4:
Channel 3, 8: Channel 4, …, 800:
Channel 12).
Connect motor cable.
Motor circuit fault due to missing
motor connection (all three phases are
not connected).
Output phase
loss
3381
For more information, check the
auxiliary code.
Autophasing routine (see section
) has failed.
Autophasing
3385
Check that the motor ID run has been
successfully completed.
Clear parameter
.
Check the setting of parameter
Check the signs of measured and
estimated speeds.
Estimated and measured positions
have opposite signs.
0001
Reverse encoder cable phasing or
edit parameter
.
Check that the load torque is not
too high for the Turning mode (must
be less than 5%).
Check that the motor is not already
rotating when the autophasing
routine starts.
Motor is rotating during
autophasing.
0002
656 Fault tracing
Содержание ACS880 Series
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 ESP control program option N5600 Firmware manual ...
Страница 2: ......
Страница 4: ......
Страница 16: ...16 ...
Страница 22: ...22 ...
Страница 24: ...24 ...
Страница 44: ...44 ...
Страница 66: ...66 ...
Страница 148: ...148 ...
Страница 167: ...Fieldbus control macro This application macro is not supported by the current firmware version Application macros 167 ...
Страница 168: ...168 ...
Страница 704: ...704 ...
Страница 728: ...728 ...
Страница 742: ...742 ...
Страница 762: ...762 ...