What to do
Cause
Event name /
Aux. code
Code
(hex)
Restore the template program or
download the program to the drive.
Program corrupted or block
non-existent.
000E
Remove blocks until the error stops.
Program too large.
0011
Correct the program and download
it to the drive.
Program is empty.
0012
Edit the program to correct the
parameter reference, or to use an
existing block.
A nonexisting parameter or block is
used in the program.
001C
Edit the program to correct the
parameter reference.
Parameter type invalid for selected
pin.
001D
Check the parameter reference in
the program.
Output to parameter failed because
the parameter was write-protected.
001E
Check for other sources affecting
the target parameter.
Adapt the program to current block
library and firmware version.
Program file incompatible with
current firmware version.
0023, 0024
Edit the program to reduce the
number of blocks.
Too many blocks.
002A
Switch off the power to the control
unit and reinstall the memory unit.
The memory unit was detached when
the control unit was powered.
Memory unit
detached
64B0
In case the memory unit was not
actually removed when the fault
occurred, check that the memory unit
is properly inserted into its connector
and its mounting screw is tight.
Reboot the control unit (using
parameter
)
or by cycling power. If the problem
persists, contact your local ABB
representative.
Reboot the control unit (using
parameter
)
Internal fault.
Internal SSW
fault
64B1
or by cycling power. If the problem
persists, contact your local ABB
representative.
Ensure that a valid user parameter set
exists. Reload if uncertain.
Loading of user parameter set failed
because
User set fault
64B2
•
set is not compatible with control
program
•
drive was switched off during
loading.
Reboot the control unit (using
parameter
)
Operating system error.
Kernel
overload
64E1
or by cycling power. If the problem
persists, contact your local ABB
representative.
An active fault has been reset.
Informative fault.
Fault reset
64FF
Try forcing a save using parameter
. Retry.
Parameter load or save failed.
Parameter
system
6581
664 Fault tracing
Содержание ACS880 Series
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 ESP control program option N5600 Firmware manual ...
Страница 2: ......
Страница 4: ......
Страница 16: ...16 ...
Страница 22: ...22 ...
Страница 24: ...24 ...
Страница 44: ...44 ...
Страница 66: ...66 ...
Страница 148: ...148 ...
Страница 167: ...Fieldbus control macro This application macro is not supported by the current firmware version Application macros 167 ...
Страница 168: ...168 ...
Страница 704: ...704 ...
Страница 728: ...728 ...
Страница 742: ...742 ...
Страница 762: ...762 ...