Def / Type
FbEq 16b / 32b
Description
Name / Range /
Selection
No.
5
Drive generates an
warning.
This only occurs if control is expected from the FBA B
interface, or if supervision is forced using parameter
50.56 FBA B comm supervision force
.
WARNING!
Make sure that it is safe to continue operation
in case of a communication break.
Warning
0.3 s / uint16
Defines the time delay before the action defined by
parameter
is taken. Time
count starts when the communication link fails to
update the message.
As a rule of thumb, this parameter should be set to at
least 3 times the transmit interval of the master.
Note: There is a 60-second boot-up delay immediately
after power-up. During the delay, the communication
break monitoring is disabled (but communication itself
can be active).
FBA B comm loss
timeout
50.33
10 = 1 s / 10 = 1 s
Time delay.
0.1 s
Auto / uint16
Selects the type and scaling of reference 1 received
from fieldbus adapter B.
See parameter
FBA B ref1 type
50.34
Auto / uint16
Selects the type and scaling of reference 2 received
from fieldbus adapter B.
See parameter
FBA B ref2 type
50.35
Auto / uint16
Selects the type/source and scaling of actual value 1
transmitted to the fieldbus network through fieldbus
adapter B.
See parameter
FBA B actual 1 type
50.37
Auto / uint16
Selects the type/source and scaling of actual value 2
transmitted to the fieldbus network through fieldbus
adapter B.
See parameter
.
FBA B actual 2 type
50.38
Not selected / uint32
Selects the source of the fieldbus status word when
the fieldbus adapter is set to a transparent
communication profile eg. by its configuration
parameters (group
FBA B SW
transparent source
50.39
0
No source selected.
Not selected
See
Terms and abbreviations (page 169)
Other [value]
Not selected / uint32
When parameter
is set to
or
, this parameter selects the
source of actual value 1 transmitted to the fieldbus
network through fieldbus adapter B.
FBA B act1
transparent source
50.40
0
No source selected.
Not selected
See
Terms and abbreviations (page 169)
Other [value]
Parameters 469
Содержание ACS880 Series
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 ESP control program option N5600 Firmware manual ...
Страница 2: ......
Страница 4: ......
Страница 16: ...16 ...
Страница 22: ...22 ...
Страница 24: ...24 ...
Страница 44: ...44 ...
Страница 66: ...66 ...
Страница 148: ...148 ...
Страница 167: ...Fieldbus control macro This application macro is not supported by the current firmware version Application macros 167 ...
Страница 168: ...168 ...
Страница 704: ...704 ...
Страница 728: ...728 ...
Страница 742: ...742 ...
Страница 762: ...762 ...