Def / Type
FbEq 16b / 32b
Description
Name / Range /
Selection
No.
Minimum torque 1 /
uint32
Selects a source that switches between two different
predefined minimum torque limits.
0 = Minimum torque limit defined by
is active
1 = Minimum torque limit selected by
is active
The user can define two sets of torque limits, and
switch between the sets using a binary source such as
a digital input.
The minimum limit selection (
) is independent of
the maximum limit selection (
).
The first set of limits is defined by parameters
and
. The second set has selector parameters for
both the minimum (
) limits
that allows the use of a selectable analog source (such
as an analog input).
User-defined
minimum torque
limit
User-defined
maximum torque
limit
30.21
30.18
30.22
30.25
30.24
30.23
0
AI1
AI1
AI2
PID
Other
Other
PID
AI2
0
30.19
30.20
0
1
1
0
The limit selection parameters are updated on a 10 ms
time level.
Note: In addition to the user-defined limits, torque may
be limited for other reasons (such as power limitation).
Refer to the block diagram on page
Minimum torque sel
30.18
0
0 (minimum torque limit defined by
is active).
Minimum torque 1
1
1 (minimum torque limit selected by
is active).
Minimum torque 2
source
2
Digital input DI1 (
, bit 0).
DI1
3
Digital input DI2 (
, bit 1).
DI2
4
Digital input DI3 (
, bit 2).
DI3
5
Digital input DI4 (
, bit 3).
DI4
Parameters 361
Содержание ACS880 Series
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 ESP control program option N5600 Firmware manual ...
Страница 2: ......
Страница 4: ......
Страница 16: ...16 ...
Страница 22: ...22 ...
Страница 24: ...24 ...
Страница 44: ...44 ...
Страница 66: ...66 ...
Страница 148: ...148 ...
Страница 167: ...Fieldbus control macro This application macro is not supported by the current firmware version Application macros 167 ...
Страница 168: ...168 ...
Страница 704: ...704 ...
Страница 728: ...728 ...
Страница 742: ...742 ...
Страница 762: ...762 ...