Def / Type
FbEq 16b / 32b
Description
Name / Range /
Selection
No.
5.0 s / real32
Defines safe motor speed ramp setting used when
automatic process control mode is active.
In order to prevent undesired speed steps due to
process feedback signal errors or any other reason, it
is recommended to set this parameter value as high
as it seems reasonable it terms of expected speed
change dynamics.
Auto mode motor
ramp time
76.19
10 = 1 s / 1 = 1 s
Auto mode motor ramp time.
0.0 ... 30000.0 s
Off / unit32
Selects the source to invert process PI controller error
sign.
Invert PI error sign
76.29
0
Invert process controller error sign is inactive.
Off
1
Inverts both Process1 and Process 2.
Invert both
2
Invert process 1 control error sign.
Invert process 1
3
Invert process 2 control error sign.
Invert process 2
Estimated flowrate /
unit16
Defines the source for the process 1 feedback signal.
Process 1 control
feedback src
76.31
0
None
NULL
1
12.12 AI1 scaled value (page 226)
AI1 scaled
2
12.22 AI2 scaled value (page 228)
.
AI1 scaled
4
3.5 FB A reference 1 (page 179)
FB A1 ref
5
3.6 FB A reference 2 (page 179)
FB A2 ref
8
3.9 EFB reference 1 (page 179)
.
EFB ref1
9
3.10 EFB reference 2 (page 179)
.
EFB ref2
7
Parameter
Estimated current
8
Estimated motor current in % of nominal motor current.
Motor current %
9
Signal
85.91 Flowrate actual is used as the process
feedback source.
Estimated flowrate
10
Signal
85.92 Head actual is used as the process
feedback source.
Estimated head
See
Terms and abbreviations (page 169)
Other [bit]
0.00 / real32
Defines the value for the process 1 reference set point.
Process 1 control set
point
76.33
100 = 1 / 10 = 1
Process 1 control set point.
0.00 ... 3000000.00
1000.0 / real32
Defines the value for the process 1 feedback and
reference unit scaling.
It is assumed that the process signal might change in
range from 0 to a value set in this parameter. This
setting only serves for rendering process unit to the
percent scale and does not limit the input in any way.
Note: When this parameter is set to 0, the process 1
feedback and set point reference scaling is bypassed.
The values are then taken to the process PI controller
input.
Process 1 max scale
76.35
Parameters 533
Содержание ACS880 Series
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 ESP control program option N5600 Firmware manual ...
Страница 2: ......
Страница 4: ......
Страница 16: ...16 ...
Страница 22: ...22 ...
Страница 24: ...24 ...
Страница 44: ...44 ...
Страница 66: ...66 ...
Страница 148: ...148 ...
Страница 167: ...Fieldbus control macro This application macro is not supported by the current firmware version Application macros 167 ...
Страница 168: ...168 ...
Страница 704: ...704 ...
Страница 728: ...728 ...
Страница 742: ...742 ...
Страница 762: ...762 ...