Def / Type
FbEq 16b / 32b
Description
Name / Range /
Selection
No.
Enables/Disables Underload and Overload protection
functions.
Load protection
79
See section Underload and overload protection.
0.00% / real32
Defines speed point 1 for the load curve.
Load curve speed
point 1
79.01
10 = 1% / 100 = 1%
Load curve speed point 1.
0.00 ... 1200.00%
0.00% / real32
Defines speed point 2 for the load curve.
Load curve speed
point 2
79.02
10 = 1% / 100 = 1%
Load curve speed point 2.
0.00 ... 1200.00%
0.00% / real32
Defines speed point 3 for the load curve.
Load curve speed
point 3
79.03
10 = 1% / 100 = 1%
Load curve speed point 3.
0.00 ... 1200.00%
0.00% / real32
Defines speed point 4 for the load curve.
Load curve speed
point 4
79.04
10 = 1% / 100 = 1%
Load curve speed point 4.
0.00 ... 1200.00%
0.00% / real32
Defines speed point 5 for the load curve.
Load curve speed
point 5
79.05
10 = 1% / 100 = 1%
Load curve speed point 5.
0.00 ... 1200.00%
100.00% / real32
Defines speed scale value for the corresponding
underload and overload limit calculation in case user
Load limit speed
scale
79.09
chooses to use Linear or Quadratic predefined load
curve shape.
This can be used together with parameter
and
.
10 = 1% / 100 = 1%
Load limit speed scale.
0.00 ... 1200.00%
ESP CW bit 7 / unit32
Defines source for underload protection enable signal.
For further information, see section Underload ride
through recovery sequence.
Underload
protection enable
79.10
0
Underload protection enable signal is inactive.
Not selected
1
Underload protection enable signal is active.
Selected
2
Digital input DI1 (
, bit 0).
DI1
3
Digital input DI2 (
, bit 1).
DI2
4
Digital input DI3 (
, bit 2).
DI3
5
Digital input DI4 (
, bit 3).
DI4
6
Digital input DI5 (
, bit 4).
DI5
7
Digital input DI6 (
, bit 5).
DI6
10
Digital input/output DIO1 (
, bit
0).
DIO1
11
Digital input/output DIO2 (
, bit
1).
DIO2
12
Parameter
74.1 ESP control word (page 519)
, bit 7 status
controls enable/disable status of the function.
ESP CW bit 7
See
Terms and abbreviations (page 169)
Other [bit]
Parameters 537
Содержание ACS880 Series
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 ESP control program option N5600 Firmware manual ...
Страница 2: ......
Страница 4: ......
Страница 16: ...16 ...
Страница 22: ...22 ...
Страница 24: ...24 ...
Страница 44: ...44 ...
Страница 66: ...66 ...
Страница 148: ...148 ...
Страница 167: ...Fieldbus control macro This application macro is not supported by the current firmware version Application macros 167 ...
Страница 168: ...168 ...
Страница 704: ...704 ...
Страница 728: ...728 ...
Страница 742: ...742 ...
Страница 762: ...762 ...