![ABB ACS880 Series Скачать руководство пользователя страница 554](http://html.mh-extra.com/html/abb/acs880-series/acs880-series_firmware-manual_2617554.webp)
Def / Type
FbEq 16b / 32b
Description
Name / Range /
Selection
No.
11
Digital input/output DIO2 (
, bit
1).
DIO2
12
Parameter
74.1 ESP control word (page 519)
, bit 12 status
controls enable/disable status of the function.
ESP CW bit 12
See
Terms and abbreviations (page 169)
Other [bit]
0.00 hour / real32
Defines time setting for periodic cleaning schedule.
When parameter
time counter
reaches the value set in this parameter, the cleaning
request is automatically generated.
After cleaning operation is completed, the timer is then
reset for another round with parameter
which displays remaining time till the next
cleaning request based on this parameter time setting.
Note: For the time trigger to work, parameter
, bit-2 must be set to 1.
Time trigger
81.19
100 = 1 hour / 100 = 1
hour
Time trigger in hours.
0.00 ... 650.00 hour
1 / real32
Defines the desired quantity of cleaning cycles.
Each cycle consists of two speed steps with period of
off-time after each step. The period and dynamics of
each cycle are defined with parameters
Number of cleaning
cycles
81.20
1 = 1 / 1 = 1
Number of cleaning cycles.
0...65000
-10.00% / real32
Defines speed reference for the first step of cleaning
cycle.
Note that the parameter
setting
is also taken into use for the cleaning operation.
First step reference
81.21
100 = 1% / 100 = 1%
First step reference in percentage.
-300.00 ... 300.00%
5.0 s / real32
Defines the time period for the first step of cleaning
cycle.
First step time
81.22
10 = 1 s / 10 = 1 s
First step time in second.
0.0 ... 6500.0 s
5.0 s / real32
Defines the time period for the pause after each step.
The speed reference will be zero during Off time.
Off time
81.23
10 = 1 s / 1 = 1 s
Off time in seconds.
0.0 ... 6500.0 s
10.00% / real32
Defines speed reference for the second step of cleaning
cycle.
Note that the parameter
setting
is also taken into use for the cleaning operation.
Second step
reference
81.24
10 = 1% / 100 = 1%
Second step reference in percentage.
-300.00 ... 300.00%
5.0 s / real32
Defines the time period for the second step of cleaning
cycle.
Second step time
81.25
10 = 1 s / 10 = 1 s
Second step time in seconds.
0.0 ... 6500.0 s
20.00 s / real32
Defines acceleration time for the cleaning operation.
Cleaning acc time
81.31
1 = 1 s / 100 = 1 s
Cleaning acceleration time in seconds.
0.00 ... 30000.00 s
20.00 s / real32
Defines deceleration time for the cleaning operation.
Cleaning dec time
81.32
554 Parameters
Содержание ACS880 Series
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 ESP control program option N5600 Firmware manual ...
Страница 2: ......
Страница 4: ......
Страница 16: ...16 ...
Страница 22: ...22 ...
Страница 24: ...24 ...
Страница 44: ...44 ...
Страница 66: ...66 ...
Страница 148: ...148 ...
Страница 167: ...Fieldbus control macro This application macro is not supported by the current firmware version Application macros 167 ...
Страница 168: ...168 ...
Страница 704: ...704 ...
Страница 728: ...728 ...
Страница 742: ...742 ...
Страница 762: ...762 ...