![ABB ACS880 Series Скачать руководство пользователя страница 360](http://html.mh-extra.com/html/abb/acs880-series/acs880-series_firmware-manual_2617360.webp)
Def / Type
FbEq 16b / 32b
Description
Name / Range /
Selection
No.
-50.00; -60.00 (95.20
b0) Hz / real32
Defines the minimum allowed frequency.
WARNING!
This value must not be higher than
.
WARNING!
This limit is effective in frequency control mode
only.
Minimum frequency
30.13
- / -
Minimum frequency. For scaling, see parameter
-598.00 ... 598.00 Hz
50.00; 60.00 (95.20
b0) Hz / real32
Defines the maximum allowed frequency.
WARNING!
This value must not be lower than
.
WARNING!
This limit is effective in frequency control mode
only.
Maximum frequency
30.14
- / -
Maximum frequency. For scaling, see parameter
-598.00 ... 598.00 Hz
Disable / uint16
A temporary motor current limit specifically for starting
can be defined by this parameter and
.
When this parameter is set to
, the drive observes
the start current limit defined by
. The limit is in force for 2 seconds after initial
magnetization (of an asynchronous induction motor)
or autophasing (of a permanent magnet motor), but
not more often than once in every 7 seconds. Otherwise,
the limit defined by
is in force.
Note: The availability of a start current higher than the
general limit depends on drive hardware. See the rating
data in the hardware manual of the drive.
Maximum start
current enable
30.15
0
Start current limit disabled.
Disable
1
Start current limit enabled.
Enable
0.00 A / real32
Defines a maximum start current when enabled by
parameter
30.15 Maximum start current enable
Maximum start
current
30.16
1 = 1 A / 1 = 1 A
Maximum start current.
0.00 ... 30000.00 A
0.00 A / real32
Defines the maximum allowed motor current.
Maximum current
30.17
1 = 1 A / 1 = 1 A
Maximum motor current.
0.00 ... 30000.00 A
360 Parameters
Содержание ACS880 Series
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 ESP control program option N5600 Firmware manual ...
Страница 2: ......
Страница 4: ......
Страница 16: ...16 ...
Страница 22: ...22 ...
Страница 24: ...24 ...
Страница 44: ...44 ...
Страница 66: ...66 ...
Страница 148: ...148 ...
Страница 167: ...Fieldbus control macro This application macro is not supported by the current firmware version Application macros 167 ...
Страница 168: ...168 ...
Страница 704: ...704 ...
Страница 728: ...728 ...
Страница 742: ...742 ...
Страница 762: ...762 ...