What to do
Cause
Event name /
Aux. code
Code
(hex)
Check the input voltage setting in
parameter
Check the input voltage.
If the problem persists, contact your
local ABB representative.
The voltage of the intermediate DC
circuit has not yet risen to operating
level.
Note: This warning can be shown only
when the IGBT supply unit is not
modulating.
DC not
charged
AE0B
Check DC fuses.
Check converter module connections
to DC link.
DC link voltage difference detected by
the branching unit.
BU DC link
difference
AE0C
Check AC fuses.
Check supply cable.
Main voltage difference detected by
the branching unit.
BU voltage
difference
AE0D
Check ambient conditions.
Check air flow and fan operation.
Check heatsink fins for dust pick-up.
Check motor power against IGBT
supply unit power.
Power unit module temperature is
excessive.
Excess
temperature
AE14
Check the cabling.
Check cooling of power module(s).
High temperature difference between
the IGBTs of different phases.
Excess
temperature
difference
AE15
Check ambient conditions.
Check air flow and fan operation.
Check heatsink fins for dust pick-up.
Check motor power against IGBT
supply unit power.
IGBT temperature is excessive.
IGBT
temperature
AE16
Define the supply voltage range
(parameter
The supply voltage range has not been
defined.
Voltage
category
unselected
AE24
Check that it is safe to continue
operation.
Return emergency stop push button
to normal position.
Restart the drive.
Supply unit has received an emergency
stop (mode selection off2) command.
Emergency
stop (OFF2)
AE58
Check module cooling air flow and fan
operation.
Check ambient temperature. If it
exceeds 40 °C (104 °F), ensure that
load current does not exceed derated
load capacity.
See appropriate hardware manual.
Check inside of cabinet and heatsink
of supply module for dust pick-up.
Clean whenever necessary.
Supply module temperature is
excessive due to eg, module overload
or fan failure.
Temperature
Warning
AE5F
Check the auxiliary code in the
line-side converter program to identify
the fan.
Check fan operation and connection.
Replace fan if faulty.
Cooling fan is stuck or disconnected.
Fan
AE73
Resynchronize the IGBT supply unit to
the grid after net lost.
Net lost is detected.
Net lost
AE78
698 Fault tracing
Содержание ACS880 Series
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 ESP control program option N5600 Firmware manual ...
Страница 2: ......
Страница 4: ......
Страница 16: ...16 ...
Страница 22: ...22 ...
Страница 24: ...24 ...
Страница 44: ...44 ...
Страница 66: ...66 ...
Страница 148: ...148 ...
Страница 167: ...Fieldbus control macro This application macro is not supported by the current firmware version Application macros 167 ...
Страница 168: ...168 ...
Страница 704: ...704 ...
Страница 728: ...728 ...
Страница 742: ...742 ...
Страница 762: ...762 ...