Def / Type
FbEq 16b / 32b
Description
Name / Range /
Selection
No.
Various hardware-related settings.
HW configuration
95
Not given / uint16
Selects the supply voltage range. This parameter is
used by the drive to determine the nominal voltage of
Supply voltage
95.1
the supply network. The parameter also affects the
current ratings and the DC voltage control functions
(trip and brake chopper activation limits) of the drive.
WARNING! An incorrect setting may cause the
motor to rush uncontrollably, or the brake
chopper or resistor to overload.
Note: The selections shown depend on the hardware
of the drive. If only one voltage range is valid for the
drive in question, it is selected by default.
Note: This parameter cannot be changed while the
drive is running.
0
No voltage range selected. The drive will not start
modulating before a range is selected.
Not given
1
208…240 V
208...240 V
2
380...415 V
380...415 V
3
440...480 V
440...480 V
4
500 V
500 V
5
525...600 V
525...600 V
6
660...690 V
660...690 V
Disable; Enable
(95.20 b15) / uint16
Enables adaptive voltage limits.
Adaptive voltage limits can be used if, for example, an
IGBT supply unit is used to raise the DC voltage level.
Adaptive voltage
limits
95.2
If the communication between the inverter and the
IGBT supply unit is active (
the voltage limits are related to the DC voltage
reference transmitted to the supply unit (
) assuming that the reference is high
enough. Otherwise, the limits are calculated based on
the measured DC voltage at the end of the pre-charging
sequence.
This function is also useful if the AC supply voltage to
the drive is high, as the warning levels are raised
accordingly.
*Affected by
, bit 15.
0
Adaptive voltage limits disabled.
Disable
1
Adaptive voltage limits enabled.
Enable
Internal 24V (ZCU);
External 24V (BCU;
95.20 b4) / uint16
Specifies how the control unit of the drive is powered.
*The default value depends on the type of control unit
and the setting of parameter
, bit 4.
Control board
supply
95.4
592 Parameters
Содержание ACS880 Series
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 ESP control program option N5600 Firmware manual ...
Страница 2: ......
Страница 4: ......
Страница 16: ...16 ...
Страница 22: ...22 ...
Страница 24: ...24 ...
Страница 44: ...44 ...
Страница 66: ...66 ...
Страница 148: ...148 ...
Страница 167: ...Fieldbus control macro This application macro is not supported by the current firmware version Application macros 167 ...
Страница 168: ...168 ...
Страница 704: ...704 ...
Страница 728: ...728 ...
Страница 742: ...742 ...
Страница 762: ...762 ...