37.21 (%)
37.31 (%)
37.35 (%)
37.25 (%)
OVERLOAD
UNDERLOAD
37.11 (rpm)
37.16 (Hz)
37.12
37.17
37.13
37.18
37.14
37.19
37.15
37.20
ALLOWED
OPERATION
Speed
Frequency
Monitored signal (37.02)
The action (none, warning or fault) taken when the signal exits the allowed
operation area can be selected separately for overload and underload conditions
(parameters
and
respectively). Each condition also has an optional timer
to delay the selected action (
and
Settings and diagnostics
Parameter group:
.
Events:
A6E6 ULC configuration (page 679)
,
,
,
and
■
Automatic fault resets
WARNING!
Before you activate the function, make sure that no dangerous situations
can occur. The function resets the drive automatically and continues
operation after a fault.
The drive can automatically reset itself after overcurrent, overvoltage, undervoltage
and external faults. The user can also specify a fault (excluding Safe torque off
related faults) to be reset automatically.
By default, automatic resets are off and must be specifically activated by the user.
134 Program features
Содержание ACS880 Series
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 ESP control program option N5600 Firmware manual ...
Страница 2: ......
Страница 4: ......
Страница 16: ...16 ...
Страница 22: ...22 ...
Страница 24: ...24 ...
Страница 44: ...44 ...
Страница 66: ...66 ...
Страница 148: ...148 ...
Страница 167: ...Fieldbus control macro This application macro is not supported by the current firmware version Application macros 167 ...
Страница 168: ...168 ...
Страница 704: ...704 ...
Страница 728: ...728 ...
Страница 742: ...742 ...
Страница 762: ...762 ...