![ABB ACS880 Series Скачать руководство пользователя страница 737](http://html.mh-extra.com/html/abb/acs880-series/acs880-series_firmware-manual_2617737.webp)
■
Contents of the fieldbus Status word (ABB Drives profile)
The upper case boldface text refers to the states shown in the state diagram (page
STATE/Description
Value
Name
Bit
READY TO SWITCH ON.
1
Ready to switch
ON
0
NOT READY TO SWITCH ON.
0
READY TO OPERATE.
1
Ready run
1
OFF1 ACTIVE.
0
OPERATION ENABLED.
1
Ready ref
2
OPERATION INHIBITED. See parameters
and
6.25 Drive inhibit status word 2
for the inhibiting condition.
0
FAULT.
1
Tripped
3
No fault.
0
OFF2 inactive.
1
Off 2 inactive
4
OFF2 ACTIVE.
0
OFF3 inactive.
1
Off 3 inactive
5
OFF3 ACTIVE.
0
SWITCH-ON INHIBITED.
1
Switch-on
inhibited
6
–
0
Warning active.
1
Warning
7
No warning active.
0
OPERATING. Actual value equals reference = is within
tolerance limits (see parameters
1
At setpoint
8
Actual value differs from reference = is outside toler-
ance limits.
0
Drive control location: REMOTE (EXT1 or EXT2).
1
Remote
9
Drive control location: LOCAL.
0
See parameter
-
Above limit
10
See parameter
.
-
User bit 0
11
See parameter
.
-
User bit 1
12
See parameter
.
-
User bit 2
13
See parameter
.
-
User bit 3
14
Reserved.
15
Fieldbus control through a fieldbus adapter 737
Содержание ACS880 Series
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 ESP control program option N5600 Firmware manual ...
Страница 2: ......
Страница 4: ......
Страница 16: ...16 ...
Страница 22: ...22 ...
Страница 24: ...24 ...
Страница 44: ...44 ...
Страница 66: ...66 ...
Страница 148: ...148 ...
Страница 167: ...Fieldbus control macro This application macro is not supported by the current firmware version Application macros 167 ...
Страница 168: ...168 ...
Страница 704: ...704 ...
Страница 728: ...728 ...
Страница 742: ...742 ...
Страница 762: ...762 ...