Def / Type
FbEq 16b / 32b
Description
Name / Range /
Selection
No.
100 % / uint16
Defines the motor load curve together with parameters
and
. The load
curve is used by the motor thermal protection model
to estimate the motor temperature.
When the parameter is set to 100%, the maximum load
is taken as the value of parameter
(higher loads heat up the motor). The load curve
level should be adjusted if the ambient temperature
differs from the nominal value set in
I = Motor current
I
N
= Nominal motor current
Drive output
frequency
I/I
N
(%)
150
100
50
35.52
35.53
35.51
Motor load curve
35.51
1 = 1 % / 1 = 1 %
Maximum load for the motor load curve.
50...150 %
70 % / uint16
Defines the motor load curve together with parameters
and
. Defines
the maximum motor load at zero speed of the load
curve. A higher value can be used if the motor has an
external motor fan to boost the cooling. See the motor
manufacturer's recommendations.
See parameter
Zero speed load
35.52
1 = 1 % / 1 = 1 %
Zero speed load for the motor load curve.
25...150 %
45.00 Hz / uint16
Defines the motor load curve together with parameters
and
Defines the break point frequency of the load curve i.e.
the point at which the motor load curve begins to
decrease from the value of parameter
towards the value of parameter
See parameter
Break point
35.53
- / -
Break point for the motor load curve. For scaling, see
parameter
1.00 ... 500.00 Hz
406 Parameters
Содержание ACS880 Series
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 ESP control program option N5600 Firmware manual ...
Страница 2: ......
Страница 4: ......
Страница 16: ...16 ...
Страница 22: ...22 ...
Страница 24: ...24 ...
Страница 44: ...44 ...
Страница 66: ...66 ...
Страница 148: ...148 ...
Страница 167: ...Fieldbus control macro This application macro is not supported by the current firmware version Application macros 167 ...
Страница 168: ...168 ...
Страница 704: ...704 ...
Страница 728: ...728 ...
Страница 742: ...742 ...
Страница 762: ...762 ...