![ABB ACS880 Series Скачать руководство пользователя страница 461](http://html.mh-extra.com/html/abb/acs880-series/acs880-series_firmware-manual_2617461.webp)
Def / Type
FbEq 16b / 32b
Description
Name / Range /
Selection
No.
No action / uint16
Selects how the drive reacts to a control panel (or PC
tool) communication break. This action is taken when
•
the panel is parametrized as an alternative control
or reference source but is not currently the active
source, and
•
communication supervision for the active control
location is not forced by parameter
Secondary comm.
loss action
49.8
0
No action taken.
No action
5
Drive generates an
warning.
WARNING!
Make sure that it is safe to continue operation
in case of a communication break.
Warning
rpm / uint16
Defines the unit for speed reference when given from
the control panel.
Panel speed
reference unit
49.14
0
rpm.
rpm
1
Percent of parameter
.
%
-30000.00 rpm /
real32
Defines a minimum limit for control panel speed
reference in external control.
In local control, the limits in parameter group
are in force. See section
Minimum ext speed
ref panel
49.15
- / -
Minimum speed reference. For scaling, see parameter
-30000.00 ...
30000.00 rpm
30000.00 rpm /
real32
Defines a maximum limit for control panel speed
reference in external control.
In local control, the limits in parameter group
are in force. See section
Maximum ext speed
ref panel
49.16
- / -
Maximum speed reference. For scaling, see parameter
-30000.00 ...
30000.00 rpm
-500.00 Hz / real32
Defines a minimum limit for control panel frequency
reference in external control.
In local control, the limits in parameter group
are in force. See section
Minimum ext
frequency ref panel
49.17
- / -
Minimum frequency reference. For scaling, see
parameter
.
-598.00 ... 598.00 Hz
500.00 Hz / real32
Defines a maximum limit for control panel frequency
reference in external control.
In local control, the limits in parameter group
are in force. See section
Maximum ext
frequency ref panel
49.18
- / -
Maximum frequency reference. For scaling, see
parameter
.
-598.00 ... 598.00 Hz
Parameters 461
Содержание ACS880 Series
Страница 1: ... ABB INDUSTRIAL DRIVES ACS880 ESP control program option N5600 Firmware manual ...
Страница 2: ......
Страница 4: ......
Страница 16: ...16 ...
Страница 22: ...22 ...